5) Steuerhardware und Hardware-Konfiguration der I/O Steuerkanäle
5) Control-board: hardware and I/O channel configuration
I/O channel configuration is a combination of hardware and software setting
For software parameter setting see chapter:
10) Parameter group 300: Configuration of digital I/O channels
11) Parameter group 400: Configuration of analogue I/O channels
Two different type of control boards are used in E800 inverter concept:
Control board for inverter 0,2 - 22 kW:
Framesize E1 - E6
Control board for inverter 30kW - 90 kW:
Framesize C3 – C6
Control board
0,2...22kW
SZ E1 - E6:
Digital input channels:
E1 - E6:
A total of 5 digital input channels DI1.....DI5 are available on inverter, size
E1-E6.
Different functions can be assigned to
these inputs, programming the parameter
F316….F320
– description: see chapter
10) Parameter group 300: Configuration of
digital I/O channels
Attention:
A function can be assigned to one single digital input only (no multiple inputs for same function allowed) If a
function is already assigned to a certain input (due to factory set), this assignment must be deleted (set function-code
to 0), before assigning to another input.
HIGH/LOW active (PNP/NPN) control-mode selection:
This selection is done via hardware setting of the
NPN-PNP DIP-
SWITCH
on the control board.
All digital inputs are isolated from analogue ground, the
24 V (50mA)
auxiliary power supply may be used for input control in
PNP mode.
CM
is the common reference point for all digital inputs
.
E800 – Rev.01 -D- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
- 23 -