10) Parametergruppe 300: Digital I/O Konfiguration
Activation and configuration of the "S" shaped ramp
F304
Initial progression
F305
Final progression
Range: 2.0....50%
Default setting 30%
F306
"S" shaped ramp activation
Selection: 0=Linear ramp
1="S" ramp
Default setting 0
Frequency threshold setting
F307
Frequency threshold 1 (Hz)
Default setting 10Hz
F308
Frequency threshold 2 (Hz)
Range: F112 - F111 (Hz)
Default setting 50Hz
F309
Hysteresis
Range: 0…100
%
Default
setting
50
%
This are frequency thresholds for signalling through programmable digital outputs - function assignation:
2 / 3
.
Hysteresis to subtract from threshold value
Current threshold
F310
Stromschwelle (A)
Range: 0…1000 A
Default setting Nennstrom
F311
Hysterese Stromschwelle
Range: 0…100
%
Default
setting
10%
Current threshold, signalled through programmable digital outputs - function assignation:
17
.
Hysteresis to subtract from threshold value
-Valid for the "end of ramp" message through digital outputs – output function assignation:
15
F312
Hysteresis to target frequency (Hz)
Range: 0.00…5.00 Hz
Default setting 0.00
- Hysteresis to subtract from threshold value
E800 – Rev.01 -D- SOFT Rev. 2.04
© 2015 EURADRIVES EURDIE GmbH
- 44 -