5) Steuerhardware und Hardware-Konfiguration der I/O Steuerkanäle
Analogue input channels:
C3 – C6:
E800 SIZE
C3…C9
have two independent analogue input channels
AI1
and
AI2
, both have a resolution of 12 Bit.
Signal level configuration is done by hardware setting on the control board, and corresponding parameter setting
For software parameter setting see: 11) Parameter group 400: Configuration of analogue I/O channels
AI1
– Voltage / Current signal:
programmable for
0…5V, 0…10V, 0...20 mA.
For
4...20 mA:
offset, to set via software
parameter
F400, F402
- (factory-default setting 0...10V)
AI2
Voltage/Current signal input:
to configure for
0…5V, 0…10V
or
0....20 mA –
For
4...20 mA:
offset, to set via software
parameter –
F406, F408
– (factory-default setting 0....20 mA)
Input impedance with voltage signal:
10 kOhm
Apparent ohmic resistance with current control:
500 Ohm