8) Parameter group 100: Basic parameters
F132
Display: Selection of operating
parameters to display during „STOP“
status (Motor stopped)
0: Target frequency / Parameter (Fxxx)
1: Jog modus via keypad - HF-0
2: Target motor speed (rpm)
4: DC-voltage
8: PID control feed back
16: Heatsink temperature
32: Reserved
64: PID Set point
128: Reserved
256: Reserved
512: Reserved
1024: Reserved
2048: Reserved
Default setting:
0+2+4
=
6
With inverter in STOP mode, the display will always show the target frequency - flashing
Following table shows the units and display-mode for various parameters:
Motorspeed (rpm):
(
NNNN
)
integer value – the decimal point indicates values above 9999.
Motor Current
A (A.A)
Motor-Voltage:
U (VVV)
Counter status:
(
ZZZZ
)
DC-Voltage:
u (VVV)
Heatsink temperature:
H (TTT)
Calculated speed
L(sss)
. Decimal point to indicate values above 999, two decimal points for values above 9999
PID controller Set-Point (normalized):
(o*.*)
PID Feed-Back (normalized):
(b *.*)
Single phase inverter size E1 (0.2 - 0.75KW) do not have temperature indication.
Parameter, for calculated speed indication (display)
F133
Transmission ratio
Range: 0.10 - 200.0
Default setting: 1.00
F134
Pulley diameter
0.001 – 1.000 (m)
Default setting: 0.001
-Example: Max. Frequency
F111=50.00Hz
, number of poles
F804=4
, transmission ration
F133=1.00
, pulley diameter R=0.05m
(
F134=0,05
), calculation result: pulley circumference: 2
π
r =2×3.14×0.05=0.314 (meter), shaft speed: 60×frequency / (number of
poles × transmission ratio) = 60×50/ (2×1.00) =1500rpm. For linear speed: speed (rpm) × pulley circumference =
1500×0.314=471(meter/second)