3. Usage
61
Code
Uni t wor ki ng stat ue
Type
01(02) Pa
01(02) Pb
01(02) Pc
Failure
01(02 ) Pd
Protection
Comprssor stops
Comprssor stops
AC over high/low voltage
protection
Unit input voltage too high or too low. Check the voltage
of unit power supply if it's higher than 264V or lower
than 180V.
Compressor shut down due to
too high/low ambient
temperature
Ambient temperature is too high or too low for unit to
work.
Compressor speed limit due to
too high/low ambient
temperature
Compressor speed down
Ambient temperature is too high or too low for unit to
work in full speed. This is a normal protection and
doesn't need any treatment.
Preserved
Preserved
Preserved
01(02) F1
01(02) F2
01(02) F3
01(02) F4
01(02) F5
01(02) F6
01(02) F7
Outdoor ambient temp. sensor
failure
Comprssor stops
Comprssor stops
Comprssor stops
Comprssor stops
Comprssor stops
Comprssor stops
Comprssor stops
Check whether ambient temperature sensor is open,
short-circuit or value drifts too much. Replace it if
necessary. If unit gives this failure code only when
compressor is working, please check whether the ambient
temperature sensor and coil temperature sensor is mixed.
Outdoor evaporator coil temp.
sensor failure
Check whether outdoor coil temperature sensor is open,
short-circuit or value drifts too much. Replace it if
necessary.
Compressor discharge temp.
sensor failure
Check whether compressor discharge temperature sensor
is open, short-circuit or value drifts too much. Replace
it if necessary.
Outdoor Suction temp. sensor
failure
Check whether outdoor suction temperature sensor is
open, short-circuit or value drifts too much. Replace it
if necessary.
Evaporating pressure sensor
failure
Check whether evaporating temperature sensor is open,
short-circuit or broken. Replace it if necessary. If unit has
no low pressure sensor, then it should be a wrong Eeprom
setting on the power PCB.
Condensing pressure sensor
failure
High pressure switch failure
(
High/low pressure switch
failure, if system has low
pressure switch)
Possible Reasons And Solutions
Compressor speed down due
to abnormal low pressure
detected by evaporating
pressure sensor
01(02 ) PE
Comprssor stops
Check whether condensing temperature sensor is open,
short-circuit or broken. Replace it if necessary. If unit
has no high pressure sensor, then it should be a wrong
Eeprom setting on the power PCB.
1.If pressure switch is in open position when unit is in
standby statue, or 2 minutes after compressor stops,
unit gives this failure. Check whether high or low
pressure switch is broken or not well connected.
2. If system gives 01(02) P5 3 times in a certain period
of time, unit stops until repowered (with 01(02) F7
failure code also shown on the display). Check
whether fan motor and water pump is working OK;
whether condensor is blocked; whether water
temperature too high, and whether water inlet&outlet
temperature has too big difference (should no bigger
than 8
℃
).
01(02) P9
Outdoor evaporator coil temp.
sensor protection
Comprssor stops
This is a protection caused by outdoor coil temperature
too high. Check whether air circulates fluently in outdoor
unit, air flow is too small, ambient temperature is too
high. If the same protection happens over 3 times in
certain period of time, unit can only be reset by repower.
Failure
Outdoor Unit Failure Codes.
This protection happens when system evaporating
pressure is higher than the set compressor speed-down
pressure point. If after slow down the compressor
speed but pressure still lower than the protection point,
compressor stops. Check whether water temperature
set value is too high; whether system water flow rate
too small; whether EEV works normally; whether air
circulates fluently in cooling mode or ambient
temperature too high in heating mode;If same
protection happens over 3 times in certain period of
time, unit shows
Fb.
01
(02)
Содержание AWH11-V5+
Страница 2: ...2 ...
Страница 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Страница 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Страница 79: ...5 1 Outlines and dimensions 5 Attached drawing Unit mm Indoor control unit 79 430 500 20 211 500 525 196 ...
Страница 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Страница 81: ...5 Attached drawing Monoblock unit AW11 V5 Unit mm 81 1204 1215 690 761 121 60 134 385 115 417 403 50 ...
Страница 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...