3. Usage
38
Timer function allows you to control different working modes at spesific hours during a 24 hour periode, for even more
energy savings. For example you can turn off hot water production in the daily hours you don
’
t use this. In the selected
periode unit will not produce hot water even hot water is selcted as working mode in your application. The setting is
repeted every 24 hours until it is disactivated.
Parameter list
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Parameter No.
Meaning
Range
Default Value
0
0
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
00 00
0(off), 1(on)
0(off), 1(on)
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
00 00-23 59
Timer function ON/OFF
Hot Water Timer ON-1
Hot Water Timer OFF-1
Hot Water Timer ON-2
Hot Water Timer OFF-2
Heating/Cooling Timer ON-1
Heating/Cooling Timer OFF-1
Heating/Cooling Timer ON-2
Heating/Cooling Timer OFF-2
Normal Shower Time (for unit with
heat recovery function only)
Anti-legionella function
Anti-legionella function starting time
Pump anti-block running time
Quiet operation starting time
Quiet operation ending time
No matter the unit is ON or OFF, press to check or actiave "Timer" parameter setting, which looks as shown below:
Value of parameter
Number of parameter
Parameter 00, value=0000
Use or to view all parameters in sequence. When the value of a parameter needs to be adjusted, press "SET"
when this parameter is shown to activate the setting of this parameter. The value start flickering.
Use to adjust setting in hours, to adjust the setting in minutes" if this parameter is a time parameter
【
】
Time&Timer Setting
Содержание AWH11-V5+
Страница 2: ...2 ...
Страница 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Страница 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Страница 79: ...5 1 Outlines and dimensions 5 Attached drawing Unit mm Indoor control unit 79 430 500 20 211 500 525 196 ...
Страница 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Страница 81: ...5 Attached drawing Monoblock unit AW11 V5 Unit mm 81 1204 1215 690 761 121 60 134 385 115 417 403 50 ...
Страница 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...