2. Installation
21
When connecting the power cable between the monoblock unit and indoor control unit, cables
connected to the terminal block in indoor control unit must match these in monoblock unit.
For example, if the terminals and power cables are connected as
→
gree/yellow cable, L
→
red cable
,
N
→
blue cable
,
the connections in the monoblock unit should be in the same way.
3) Aluminum foil electric heating piece power cable between indoor control unit and monoblock unit
Prepare a 3 cores power cable with suitable length that complies the local safety regulations,
A. Insert one end of this cable through the cable gland on top of the indoor control unit, and connect
this power cable to "Outdoor unit” on indoor control unit terminal block.
B. Fasten the cable gland to ensure the cable won't get loosen.
Connect cable between indoor control unit and monoblock unit to correspondent terminal block
according to the wiring diagram. Fasten the cable gland to ensure the cable won't get loosen.
C
.
C
B
Shown as "Outdoor unit
" on wiring diagram
G
HN
HL
For more solid connection, for that cables that need to be connected with terminals:.
1.Please try to use solid ware instead of strand wire.
2.If stranded wire is used, please make a pin terminal on the end.
3.The stripped length of the wire should be no shorter than 10mm.
A
Содержание AWH11-V5+
Страница 2: ...2 ...
Страница 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Страница 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Страница 79: ...5 1 Outlines and dimensions 5 Attached drawing Unit mm Indoor control unit 79 430 500 20 211 500 525 196 ...
Страница 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Страница 81: ...5 Attached drawing Monoblock unit AW11 V5 Unit mm 81 1204 1215 690 761 121 60 134 385 115 417 403 50 ...
Страница 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...