If 1 hour before "Normal Shower Time" set in "Time and Timer Setting" under Basic Operation , hot water temperature
has still not reached the set value, unit will activate standard hot water operation to ensure you can enjoy enough hot
shower water at/after this time.
These parameters are valid only for the units with heat recovery function. For the unit without this function, "Heat
Recovery Function" should always set to 1 (invalid).
If it is set to ON, unit will try to heat up the hot water by recover the wasted heat in heating and cooling operation.
It will turn ON heat recovery circuit if actual hot water temperature is "Hot Water Restart Based On ∆T in Heat Recovery
Operation" lower than set hot water temperature, and stop after it heat the hot water to "Hot Water Stop Based On ∆T in
Heat Recovery Operation" over set hot water temperature.
Working Procedure of Shifting Priority Function:
Parameter No.
Meaning
Range
Default Value
Working of Extra Heating Source for
Hot Water in Shifting Priority
Operation
E7
0 (no), 1(yes)
0
Parameter No.
Meaning
Range
Default Value
Hot Water Min. Working Hours in
Shifting Priority Operation
Heating Max. Working Hours in
Shifting Priority Operation
E5
E6
20 - 180 (in minutes)
20 - 180 (in minutes)
5
30
50
If "Shifting Priority" function is turned ON in "Temperature Parameter" setting under Basic Operation, when actual
ambient temperature is lower than
"
Shifting Priority" setting, Shifting Priority function will be activated.
Unit will firstly work in Hot Water Mode. If it gets the set temperature for hot water, or it has been working in Hot Water
Mode over "Hot Water Min. Working Hours in Shifting Priority Operation", and temperature for heating has dropped
over "Allowable Temp Drift In Heating in Shifting Priority Operation" based on set heating temperature, unit switch to
heating. After switch to heating operation, if it gets the set temperature for hot water, or it has been working in heating
operation for over " Heating Max
.
Working
Hours
in
Shifting
Priority
Operation
",
unit
switch
back
to
hot
water
.
This
process
will
repeat
continously
E4
Allowable Temp Drift In Heating in
Shifting Priority Operation
3 - 20 (in
℃
)
In shifting priority operation, when the unit switches to heating , this function can be activated to turn on extra heating
source for hot water, and help to reach the set temperature for hot water.
If Parameter E7 is set as 1, the extra heating source for hot water will turn on when unit switches to heating in shifting
priority operation.
If Parameter E7 is set as 0, the extra heating source for hot water will turn off when unit switches to heating in shifting
priority operation.
Note: The extra heating source for hot water should be connected to the port HTW on the indoor PCB toactivate
the function. For AWT model, this function is invalid, because 1.5KW electric heater inside the water tank is
controlled bydigital thermostat directly, and there is no other heating source connected to HTW port.
The running time for DHW
is cleared. Unit Starts heating
and counting the running time.
Unit keep on working in DHW
and counting the running time.
The ambient temp.
Is below
Whether the
unit works in
DHW
Whether unit works
in DHW over
House heating water temperature
drops over
Whether unit works in
Heating over
The running time for Heating is
cleared. Unit starts DHW and
counting the running time.
Unit keep on working in Heating
and counting the running time.
Unit works in heating
YES
NO
YES
YES
YES
YES
NO
NO
3. Usage
58
Содержание AWH11-V5+
Страница 2: ...2 ...
Страница 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Страница 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Страница 79: ...5 1 Outlines and dimensions 5 Attached drawing Unit mm Indoor control unit 79 430 500 20 211 500 525 196 ...
Страница 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Страница 81: ...5 Attached drawing Monoblock unit AW11 V5 Unit mm 81 1204 1215 690 761 121 60 134 385 115 417 403 50 ...
Страница 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...