EAV - EME/EMD Rev. A Models
Installation and Operations Manual
Section 9: On-Board Controls
Pumps
Under settings, scroll down to Pumps (after entering passcode).
•
Load Pump Min Speed:
This is the lowest % of PWM signal
the pump will run, regardless of Delta T setting.
3.6.0
3.6.1 Hot Water Setpoint
3.6.2 Hot Water Deadband
3.7.2 Load Pump Max Speed
3.7.3 Delta Temp Heat Setpoint
3.7.4 Deta Temp Cool Setpoint
3.8.1 Pressure Units
3.8.2 Replace Filter
3.9.0
3.7.0
3.7.1 Load Pump Min Speed
3.7.5 Temp Units
3.8.0
3.9.0.1
3.9.0.2
•
Load Pump Max Speed:
This is the highest % of PWM signal
the pump will run, regardless of Delta T setting.
•
Delta Temp Cool Setpoint:
This is the pump speed that will
maintain the Delta T (temperature difference) between
entering and leaving fluid temperatures. For example, if the
Delta Temp is set at 5 deg. F and the entering temperature
is 50 deg. F, the pump speed will increase/decrease RPM to
attempt to deliver 45 deg. F leaving fluid temperature to the
system.
•
Delta Temp Heat Setpoint:
This is the pump speed that
will maintain the Delta T (temperature difference) between
entering and leaving fluid temperatures. For example, if the
Delta Temp is set at 8 deg. F and the entering temperature
is 90 deg. F, the pump speed will increase/decrease RPM to
attempt to deliver 98 deg. F leaving fluid temperature to the
system.
Alarms
The system contains an advanced network of sensors for system
monitoring of optimal running conditions. If a problem should
occur, these sensors will quickly identify the issue. In such a
situation, the HMI displays a red LED, and flashing “ALARM” text
on the screen. Additional details about an alarm can be viewed
in “Alarm Info” under the menu.
•
Delta Temp Heat Setpoint:
This is the pump speed that
will maintain the Delta T (temperature difference) between
entering and leaving fluid temperatures. For example, if the
Delta Temp is set at 8 deg. F and the entering temperature
is 90 deg. F, the pump speed will increase/decrease RPM to
attempt to deliver 98 deg. F leaving fluid temperature to the
system.
⚠
NOTICE
⚠
THE SYSTEM WILL ADJUST PUMP SPEED TO MAINTAIN AT
LEAST 4 GPM REGARDLESS OF DELTA T OR MIN. % SETTING.