EAV - EME/EMD Rev. A Models
Installation and Operations Manual
WV Installation: Heat & Cool-with Hot Water
OPTIONAL
NON-PRESSURIZED
FLOW CENTER
TO
LOOP
FIELD
FROM
LOOP
FIELD
SOURCE IN
SOURCE OUT
P/T
P/T
P/T
P/T
SOURCE IN
SOURCE OUT
TO
LOOP
FIELD
FROM
LOOP
FIELD
FLUSH
VALVE
Typ
e XX
XX X
X-X
X X
XX
XXX
V ~
XX/XX
Hz
GFXX
X
EuP Ready
I1/1
(A)
P1(W)
X.XX
X.XX
XX
XX
Max.
Min
.
P/N:
XXX
XXXX
PC:X
XXX
XX
IP
XX
TF
XX
Max.
X.X
MPa
A
High
Effi
cienc
y
XX
EEI<0.23
NOTE 5
HYDRAULIC
SEPARATOR
RADIANT
FLOOR
HEATING
ZONE 2
RADIANT
FLOOR
HEATING
ZONE 3
HYDRONIC
AIR HANDLER
ZONE 1
DHW OUT
ΔP
LOAD OUT
NOTE 4
NOTE 7
TURBOMAX
WATER HEATER
DOMESTIC
COLD
WATER
HOT
COLD
LOAD
IN
LOAD
OUT
NOTE 6
NOTE 6
NOTE 6
MAKE-UP
WATER
SYSTEM
PUMP
USE AGFP DOUBLE O-RING X CAM
ADAPTERS IF USING FLUSH CART;
USE AGAMFH DOUBLE O-RING X
GARDEN HOSE FEMALE ADAPTERS
IF USING GARDEN HOSES.
LOAD IN
DHW IN
CLOSED
“OFF” TO
THE BOTTOM
FLUSHING
HOSES
CLOSED
UNIT DIVERTING
VALVES TO HOUSE
“OFF” TO
THE BOTTOM
OPEN
OPEN
SET TO
7.5 PSI
Figure 13c: Flushing Piping Between Indoor Module & Hydraulic Separator
Piping Diagram - Flushing Piping Between Indoor Module & Hydraulic Separator
Section 6: Unit Piping Installation