24
properties:
External diameter: 5 mm to 8 mm
Conductor cross-section: 2.5 mm² to 6 mm²
Qty single wires: at least 7
Nominal voltage: at least 600V
Procedure:
1. Strip 12 mm off the cable insulation.
2. Route the stripped cable all the way into the DC connector. Ensure that the stripped
cable and the DC connector have the same polarity.
3. Press the clamping bracket down until it audibly snaps into place.
4. Ensure that the cable is correctly positioned:
Result
Measure
If the stranded wires are visible in the
chamber of the clamping bracket, the
cable is correctly positioned.
• Proceed to step 5.
If the stranded wires are not visible in
the chamber, the cable is not correctly
positioned.
• Release the clamping bracket. To do so,
insert a flat-blade screwdriver (blade width:
3.5 mm) into the clamping bracket and lever