8
3.2 Checking for transport damage
Thoroughly inspect the packaging upon delivery. If you detect any damage to the
packaging which indicates the inverter may have been damaged, inform the
responsible shipping company immediately. We will be glad to assist you if required.
4 Mounting
4.1 Requirements for mounting
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where flammable materials are stored.
• Do not mount the inverter in areas where there is a risk of explosion.
1. Be sure the inverter is installed out of the reach of children.
2. Mount the inverter in areas where it cannot be touched inadvertently.
3. Ensure good access to the inverter for installation and possible service.
4. Make sure that heat can dissipate, observe the following minimum clearance to
walls, other inverters, or objects:
5. The ambient temperature is recommended
below 40°C to ensure optimal operation.
6. Recommend to mount the inverter under the shaded site of the building or mount
an awning above the inverter.
Direction
Min. clearance
(
mm
)
above
500
below
500
sides
300