25
it open.
• Remove the cable and go back to step 2.
5.
Push the swivel nut up to the thread and tighten (torque: 2 Nm).
5.5.3 Disassembling the DC connectors
Danger to life due to high voltages on DC conductors
When exposed to sunlight, the PV array generates dangerous DC voltage which is
present in the DC conductors. Touching the DC conductors can lead to lethal
electric shocks.
• Cover the PV modules.
• Do not touch the DC conductors.
1. Unscrew the swivel nut.
2. To release the DC connector, insert a flat-blade screwdriver (blade width: 3.5 mm)
into the side catch mechanism and lever open.