32
103448-02 - 6/13
iV. Venting
C. Polypropylene Venting (continued)
CaUTiOn
Bending or attempting to install flexible pipe if it
has been stored at ambient temperature below
41°F (5°C) will cause material to become brittle
and lead to cracks.
•
When flexible polypropylene pipe (liner) is used
for combustion product venting, it must not be
installed at an angle greater than 45 degrees
from vertical plane.
This will insure proper
condensate flow back towards the boiler.
CaUTiOn
Do not install flexible polypropylene pipe at an
angle greater than 45 degrees from vertical plane
when used for combustion product venting.
Failure to do so will result in improper condensate
drainage towards the boiler and possible
subsequent vent pipe blockage.
• When flexible polypropylene pipe (liner) is used
for
combustion air supply
to a boiler, the pipe
(liner) can be installed in vertical or horizontal
position.
•
Follow flexible polypropylene pipe (liner)
manufacturer specific installation instructions
Figure 14: Vent System Field Modification to Install PVC to PP Adapter (M&G/DuraVent Shown)
regarding application/listing, permits, minimum
clearances to combustibles; installation details
(proper joint assembly, pipe support and routing,
gasket and fitting installation, optional tooling
availability/usage, routing thru masonry chimney
for combustion product venting or, combination
of combustion product venting and combustion
air supply).
•
When there is a conflict between flexible
polypropylene pipe (liner) manufacturer
installation instructions and Alpine boiler
Installation, Operating and Service Instructions,
the more restrictive instructions shall govern.
Alpine Boiler Two-Pipe Vent System Connector Field
Modification Procedure To Accept Polypropylene Vent
Piping – Floor Mounted Boiler Builds:
Alpine floor mounted boilers are factory supplied with a
model-specific boiler two-pipe CPVC/PVC vent system
connector shipped within a model-specific boiler CPVC
gasketed vent kit carton.
Locate and remove a model-specific boiler two-pipe CPVC/
PVC vent system connector.
When using
M&G/DuraVent
polypropylene pipe for
combustion product venting modify the two-pipe vent
system connector upper vent connection port (has a flue
temperature sensor port welded on the side) to accept a
PVC to PP boiler adapter, as follows (See Figure 14 ):
Содержание ALP080B
Страница 72: ...72 103448 02 6 13 VIII Electrical continued ...
Страница 73: ...103448 02 6 13 73 VIII Electrical continued Figure 43 Wiring Connections Diagram ...
Страница 75: ...103448 02 6 13 75 VIII Electrical continued Figure 44 Ladder Diagram ...
Страница 136: ...136 103448 02 6 13 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...