iV. Venting
B. CPVC/PVC Venting (continued)
Table 8: Vent/Combustion air Pipe Length – Two-Pipe Direct Vent System Options
•
CPVC/PVC
•
Polypropylene (PP) or Polypropylene (PP)/PVC
•
Stainless Steel/PVC or Galvanized Steel)
Boiler
Model
3” (80 mm)
Combustion air Pipe
(Equivalent Length)
4” (100 mm)
Combustion air Pipe
(Equivalent Length)
3” (80 mm) Vent Pipe
(Equivalent Length)
4” (100 mm) Vent Pipe
(Equivalent Length)
Min.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
ALP080B
30 In.
135 Ft.
30 In.
135 Ft.
ALP105B
30 In.
135 Ft.
30 In.
135 Ft.
ALP150B
30 In.
135 Ft.
30 In.
135 Ft.
ALP210B
30 In.
135 Ft.
30 In.
135 Ft.
ALP285B
30 In.
100 Ft.
30 In.
100 Ft.
ALP399
30 In.
100 Ft.
30 In.
100 Ft.
Vent/Combustion Air Equivalent Length Calculation Work Sheet CPVC/PVC Two-Pipe
Combustion air
Vent
90° Elbow(s) PVC (installer Supplied)
90° Elbow(s) CPVC (Supplied with Boiler)
Nominal
Diameter, In.
Quantity
(Pc)
Equivalent
Length, Ft/Pc
Subtotal,
Equivalent
Ft. (A)
Nominal
Diameter, In.
Quantity
(Pc)
Equivalent Length,
Ft/Pc
Subtotal,
Equivalent Ft.
(D)
3
10
3
1
10
10
4
13
4
1
13
13
45° Elbow(s) PVC (installer Supplied)
90° Elbow(s) PVC (installer Supplied)
Nominal
Diameter, In.
Quantity
(Pc)
Equivalent
Length, Ft/Pc
Subtotal,
Equivalent
Ft. (B)
Nominal
Diameter, In.
Quantity
(Pc)
Equivalent Length,
Ft/Pc
Subtotal,
Equivalent Ft.
(A)
3
3.0
3
10
4
4.5
4
13
Straight Pipe, PVC (installer Supplied)
45° Elbow(s) PVC (installer Supplied)
Nominal
Diameter, In.
Quantity
(Length, Ft.)
Equivalent
Length, Ft/Ft
Subtotal,
Equivalent
Ft. (C)
Nominal
Diameter, In.
Quantity
(Length, Ft.)
Equivalent Length,
Ft/Ft
Subtotal,
Equivalent Ft.
(B)
3
1
3
3.0
4
1
4
4.5
* Total Equivalent Length, Ft. (A+B+C) =
30” (2.5 Ft.) Straight Pipe, CPVC (Supplied with Boiler)
Nominal
Diameter, In.
Quantity
(Length, Ft.)
Equivalent Length,
Ft/Ft
Subtotal,
Equivalent Ft.
(E)
3
2.5
1
2.5
4
2.5
1
2.5
Straight Pipe, PVC (installer Supplied)
Nominal
Diameter, In.
Quantity
(Length, Ft.)
Equivalent Length,
Ft/Ft
Subtotal,
Equivalent
Ft. (C)
3
1
4
1
* Total Equivalent Length, Ft. (A+B+C+D+E) =
* Note: Total Equivalent Length Calculated Value Cannot Exceed Max. Equivalent Length Values shown in Table 8.
Vent and Combustion Air Terminals Do Not Count Towards Total Equivalent Length.
Содержание ALP080B
Страница 72: ...72 103448 02 6 13 VIII Electrical continued ...
Страница 73: ...103448 02 6 13 73 VIII Electrical continued Figure 43 Wiring Connections Diagram ...
Страница 75: ...103448 02 6 13 75 VIII Electrical continued Figure 44 Ladder Diagram ...
Страница 136: ...136 103448 02 6 13 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...