Table 2a: rating Data - Models aLP080B thru aLP399 (0 to 2000 Feet Elevation above Sea Level)
Table 2B: rating Data - Models aLP080B thru aLP399 (2001 to 7000 Feet Elevation above Sea Level)
I. Product Description, Specifications and Dimensional Data
(continued)
alpine Series gas-Fired Boilers
*
Model Number
Input (MBH)
Boiler Water
Volume (Gal.)
Heat Transfer Area
(Sq. Ft.)
Min.
Max.
ALP080B
16
80
0.6
7.3
ALP105B
21
105
0.7
9.1
ALP150B
30
150
1.3
16.4
ALP210B
42
210
1.7
21.8
ALP285B
57
285
2.4
29.1
ALP399
80
399
3.4
41.8
* Add Suffix “F” for Floor mounted Models or Suffix “W” for Wall mounted Models.
notes:
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI, 80 PSI
and 100 PSI - Optional (ALP080B thru ALP285B)
Maximum Working Pressure, Water - 50 PSI Shipped from Factory (std.); 80 PSI and 100
PSI - Optional (ALP399 only)
Maximum Allowable Temperature, Water - 210°F, Maximum Firing Rate
Target Setpoint is 190°F, Automatic Reset High Limit Setpoint is 200°F and Manual Reset
High Limit Setpoint is 210°F.
Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas
application. Refer to ‘System Start-Up Section of the Installation, Operating and Service
Instructions manual for detailed procedure.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For
elevations above 2000 Feet, ratings should be reduced at the rate of four percent (4%) for
each 1000 Feet above sea level.
alpine Series gas-Fired Boilers
Model number *
input (MBH)
Boiler Water
Volume (gal.)
Heat Transfer area
(Sq. Ft.)
Min.
Max.
ALP080B
27
80
0.6
7.3
ALP105B
35
105
0.7
9.1
ALP150B
50
150
1.3
16.4
ALP210B
70
210
1.7
21.8
ALP285B
57
285
2.4
29.1
ALP399
80
399
3.4
41.8
* Add Suffix “F” for Floor mounted Models or Suffix “W” for Wall mounted Models.
notes:
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI, 80 PSI
and 100 PSI - Optional
Maximum Working Pressure, Water - 50 PSI Shipped from Factory (std.); 80 PSI and 100
PSI - Optional (ALP399 only)
Maximum Allowable Temperature, Water - 210°F, Maximum Firing Rate
Target Setpoint is 190°F, Automatic Reset High Limit Setpoint is 200°F and Manual Reset
High Limit Setpoint is 210°F.
Boilers are factory shipped as Natural Gas builds and have to be field
adjusted for LP gas application. Refer to ‘System Start-Up” Section of the
Installation, Operating and Service Instructions manual for detailed
procedure.
For elevations above 2000 Feet, ratings should be reduced at the rate of four percent (4%)
for each 1000 Feet above sea level.
Содержание ALP080B
Страница 72: ...72 103448 02 6 13 VIII Electrical continued ...
Страница 73: ...103448 02 6 13 73 VIII Electrical continued Figure 43 Wiring Connections Diagram ...
Страница 75: ...103448 02 6 13 75 VIII Electrical continued Figure 44 Ladder Diagram ...
Страница 136: ...136 103448 02 6 13 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...