Commissioning
Proline t-mass 65 PROFIBUS DP/PA
66
Hauser
7.6.2
Modules for cyclic data transmission
The measuring device is a so-called modular PROFIBUS slave. In contrast to a compact slave,
the structure of a modular slave is variable - it consists of several individual modules. In the
GSD file, the individual modules (input and output data) are described with their individual
properties. The modules are permanently assigned to the slots, i.e. the sequence or arrange-
ment of the modules must be observed when configuring the modules (see following table).
Gaps between configured modules have to be assigned the EMPTY_MODULE module.
To optimize the data throughput rate of the PROFIBUS network, it is recommended to only
configure modules that are processed in the PROFIBUS master system.
It is essential to adhere to the following sequence/assignment when configuring the mod-
ules in the PROFIBUS master system:
!
Note!
• The assignment of the measured variables for the Analog Input function blocks (1 to 3)
and the totalizer function blocks (1 to 2) can be changed by means of the CHANNEL func-
tion.
A detailed description of the individual modules is contained in the following section.
• The measuring device has to be reset once a new configuration has been loaded to the
automation system. This can be effected as follows:
– By means of the local display
– By means of an operating program (e.g. FieldCare)
– By switching the supply voltage off and on again.
Slot sequence
Module
Description
1
AI
Analog Input function block 1
Output variable
Mass flow (factory setting)
2
AI
Analog Input function block 2
Output variable
Corrected volume flow (factory setting)
3
AI
Analog Input function block 3
Output variable
Temperature (factory setting)
4
TOTAL or
SETTOT_TOTAL or
SETTOT_MODETOT_TOTAL
Totalizer function block 1
TOTAL
output variable = totalized mass flow (factory set-
ting)
SETTOT
totalizer control
MODETOT
totalizer configuration
5
TOTAL or
SETTOT_TOTAL or
SETTOT_MODETOT_TOTAL
Totalizer function block 2
TOTAL
output variable = totalized mass flow (factory set-
ting)
SETTOT
totalizer control
MODETOT
totalizer configuration
6
DISPLAY_VALUE
Value for local display
7
CONTROL_BLOCK
Control of device functions
8
PRESSURE_VALUE
Process pressure
9
FRACTION_INPUT
Analyzer input