Electrical connection
Proline t-mass 65 PROFIBUS DP/PA
36
Hauser
5.5
Post-connection check
Perform the following checks after completing electrical installation of the measuring
device:
Measuring device condition and specifications
Notes
Are the measuring device or cables undamaged (visual inspection)?
-
Electrical connection
Notes
Does the supply voltage match the specifications on the nameplate?
85 to 260 V AC (45 to 65 Hz)
20 to 55 V AC (45 to 65 Hz)
16 to 62 V DC
Do the cables comply with the specifications?
PROFIBUS DP
Do the cables have adequate strain relief?
-
Cables correctly segregated by type?
Without loops and crossovers?
-
Are the power supply and signal cables correctly connected?
See the wiring diagram inside the
cover of the terminal compartment
Only remote version: Is the flow sensor connected to the matching
transmitter electronics?
Check serial number on nameplates of
sensor and connected transmitter.
Only remote version: is the connecting cable between sensor and trans-
mitter connected correctly?
Are all screw terminals firmly tightened?
-
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?
Are all housing covers installed and firmly tightened?
-
Electrical connection, PROFIBUS
Notes
Are all the connecting components (T-boxes, junction boxes, connec-
tors, etc.) connected with each other correctly?
-
Has each fieldbus segment been terminated at both ends with a bus ter-
minator?
Has the max. length of the fieldbus cable been observed in accordance
with the PROFIBUS specifications?
Has the max. length of the spurs been observed in accordance with the
PROFIBUS specifications?
Is the fieldbus cable fully shielded and correctly grounded?