Operation
Proline t-mass 65 PROFIBUS DP/PA
46
Hauser
6.6.3
Configuring the terminating resistors
!
Note!
It is important to terminate the RS485 line correctly at the start and end of the bus segment
since impedance mismatch results in reflections on the line which can cause faulty data
transfer.
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Switch off the power
supply before you remove the cover of the electronics compartment.
• For baudrates up to 1.5 MBaud, the termination is set via the terminating switch SW 1 for
the last transmitter on the bus: ON – ON – ON – ON.
• The measuring device is operated with a baudrate >1.5 MBaud: Due to the capacitive load
of the device and the line reflection generated as a result, make sure that external termi-
nation is used.
The miniature switch for termination is located on the I/O board (see Figure):
A0005408
Fig. 32:
Set terminating resistors (for baud rates < 1.5 MBaud)
A = Factory setting
B = Setting at the last transmitter
!
Note!
It is generally recommended to use external termination since if a device that is terminated
internally is defect, this can result in the failure of the entire segment.
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
390
W
+5V
A
3
4
1
2
OFF ON
220
W
390
W
SW 1
390
W
+5V
B
3
4
1
2
OFF ON
220
W
390
W
SW 1
Содержание Proline t-mass 65 PROFIBUS DA
Страница 127: ...www addresses endress com ...