Commissioning
Proline t-mass 65 PROFIBUS DP/PA
82
Hauser
Example 2
A0005498
Fig. 43:
In this example, modules that are not needed are replaced by the module EMPTY_MODULE.
The t-mass 65 GSD file is used .
With this configuration, the Analog Input function block 1 (slot 1), the totalizer value
TOTAL (slot 4) and the cyclic control of device functions CONTROL_BLOCK (slot 7) are acti-
vated.
The mass flow (factory setting) is read out cyclically by the measuring device by means of
Analog Input function block 1. The totalizer is configured "without configuration". In other
words, in this example it only returns the totalizer value for the mass flow (factory setting)
by means of the TOTAL module and cannot be controlled by the PROFIBUS Master (class 1).
Slot
sequence
(Slot)
Module
Byte
length
input
data
Byte
length
output
data
Description
1
AI
5
-
Analog Input function block 1
Output variable
Mass flow (factory setting)
2
EMPTY
_MODULE
-
-
Empty
3
EMPTY
_MODULE
-
-
Empty
4
TOTAL
5
-
Totalizer function block 1
TOTAL
output variable = totalized mass flow (factory
setting)
5
EMPTY
_MODULE
-
-
Empty
6
EMPTY
_MODULE
-
-
Empty
7
CONTROL
_BLOCK
-
1
Control of device functions