Proline Promag L 400 HART
Technical data
Hauser
129
16.6
Performance characteristics
Reference operating
conditions
To DIN EN 29104
• Fluid temperature: +28
±
2 °C (+82
±
4 °F)
• Ambient temperature range: +22
±
2 °C (+72
±
4 °F)
• Warm-up period: 30 min
Installation
• Inlet run
>
10
´
DN
• Outlet run
>
5
´
DN
• Sensor and transmitter grounded.
• The sensor is centered in the pipe.
Maximum measured error
Accuracy of outputs
o.r. = of reading; o.f.s. = of full scale value
The outputs have the following base accuracy specifications.
Current output
Accuracy
Max.
±
0.05 % o.f.s. or
±
5 µA
Pulse/frequency output
Accuracy
Max.
±
50 ppm o.r.
Error limits under reference operating conditions
o.r. = of reading
Pulse output
• ±0.5 % o.r.
±
1 mm/s (0.04 in/s)
• Optional: ±0.2 % o.r.
±
2 mm/s (0.08 in/s)
Fluctuations in the supply voltage do not have any effect within the specified range.
2.5
[%]
2.0
1.5
1.0
0.5
0
0.2 %
0.5 %
0
1
2
4
6
8
10 [m/s]
v
5
10
15
20
25
30
32 [ft/s]
0
A0005531
å
38
Maximum measured error in % o.r.
Repeatability
o.r. = of reading
max. ±0.1 % o.r.
±
0.5 mm/s (0.02 in/s)