Commissioning
Proline Promag L 400 HART
70
Hauser
Volume flow unit
Select volume flow unit.
Result
The selected unit applies for:
– Outputs
– Low flow cutoff
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Conductivity unit
Select the unit for
conductivity.
Result
The selected unit applies for:
– Current output
– Frequency output
– Switching output
– Simulation process
variable
Unit choose list
S/m
Mass flow unit
Select the unit for mass flow.
Result
The selected unit applies for:
– Outputs
– Low flow cutoff
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Density unit
Select the unit for density.
Result
The selected unit applies for:
Fixed density
Unit choose list
Country-dependent
• kg/l
• g/cc
Fixed density
Enter the fixed value for the
density.
Max. 15-digit, positive
floating-point number
Country-dependent:
• 1 kg/l
• 1 g/cc
Current span
Select the current range for
the process value output and
for the upper and lower level
for signal on alarm.
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA
• Fixed current
Country-dependent:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
0/4 mA value
Enter the value for 0 mA
current or 4 mA current.
Max. 15-digit floating-point
number with sign
Depends on country and
nominal diameter
20 mA value
Enter 20 mA value.
Max. 15-digit floating-point
number with sign
Depends on country and
nominal diameter
Failure mode
Select the value the current
output adopts in an alarm
condition.
• Min. (only for 4-20 mA
HART)
• Max.
• Last valid value
• Actual value
• Defined value
Max.
Failure current
Select the current value the
current output adopts in an
alarm condition.
• 0-20 mA:0 to 22.5 mA
• 4-20 mA HART:
3.59 to 22.5 mA
22.5 mA
10.4.3 Configuring the pulse/frequency/switch output
The
Pulse/frequency/switch output 1-2
wizard guides you systematically through all parameters
that can be set for the configuration of the selected output type.
Navigation path
• "Setup" menu
®
Pulse/frequency/switch output 1
• "Setup" menu
®
Pulse/frequency/switch output 2