OperatingйInstructions

Proline Promag D 400

HART

Electromagneticйflowmeter

BA01061D/06/EN/03.14

71245449
Validйasйofйversion

01.00.zzйсDeviceйfirmware)

Содержание Proline Promag D 400 HART

Страница 1: ...Products Solutions Services Operating Instructions Proline Promag D 400 HART Electromagnetic flowmeter BA01061D 06 EN 03 14 71245449 Valid as of version 01 00 zz Device firmware...

Страница 2: ...er to individuals or the facility read the Basic safety instructions section carefully as well as all other safety instructions in the document that are specific to working procedures The manufacturer...

Страница 3: ...Turning the display module 28 6 3 Post installation check 29 7 Electrical connection 30 7 1 Connection conditions 30 7 1 1 Required tools 30 7 1 2 Requirements for connecting cable 30 7 1 3 Terminal a...

Страница 4: ...he display 98 11 4 Reading measured values 98 11 4 1 Process variables 98 11 4 2 Totalizer 99 11 4 3 Input values 99 11 4 4 Output values 99 11 5 Adapting the measuring device to the process condition...

Страница 5: ...Performance characteristics 131 16 7 Installation 133 16 8 Environment 133 16 9 Process 133 16 10 Mechanical construction 134 16 11 Operability 139 16 12 Certificates and approvals 141 16 13 Applicat...

Страница 6: ...result in minor or medium injury NOTICE NOTE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Symbol Meaning Direct curre...

Страница 7: ...r actions that are forbidden Tip Indicates additional information Reference to documentation Refers to the corresponding device documentation Reference to page Refers to the corresponding page number...

Страница 8: ...ll the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device Brief Operating Instructions Guide that takes you quickly to the 1...

Страница 9: ...ic applications or in applications where there is an increased risk due to process pressure are labeled accordingly on the nameplate To ensure that the measuring device remains in proper condition for...

Страница 10: ...technical condition and fail safe condition only The operator is responsible for interference free operation of the device Conversions to the device Unauthorized modifications to the device are not p...

Страница 11: ...escribed in the Operating Instructions The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings IT security measures in line with operators...

Страница 12: ...6 8 7 4 A0021563 1 Important components of the compact version 1 Display module 2 Smart sensor electronics module 3 HistoROM DAT plug in memory 4 Main electronics module 5 Terminals screw terminals s...

Страница 13: ...M might not be part of the delivery In such cases the technical documentation is available via the Internet or via the Endress Hauser Operations App see the Product identification section 14 4 2 Produ...

Страница 14: ...ber from the nameplate or scan the 2 D matrix code QR code on the nameplate 4 2 1 Transmitter nameplate Order code i Ext ord cd Ser no Patents i Date 1 2 3 4 5 6 7 8 9 10 11 12 13 A0017346 2 Example o...

Страница 15: ...reordered using the order code Extended order code The device type product root and basic specifications mandatory features are always listed Of the optional specifications optional features only the...

Страница 16: ...e measuring device is higher than the suspension points of the webbing slings Risk of injury if the measuring device slips Secure the measuring device from rotating or slipping Observe the weight spec...

Страница 17: ...e plastic pallet Plastic straps Plastic adhesive strips Dunnage Paper cushion 6 Mounting 6 1 Installation conditions 6 1 1 Mounting position Mounting location h A0023343 Preferably install the sensor...

Страница 18: ...pty pipe detection EPD function offers additional protection by detecting empty or partially filled pipes 5 DN 2 DN A0017063 Orientation The direction of the arrow on the sensor nameplate helps you to...

Страница 19: ...nstallation lengths of the device see the Technical Information document Mechanical construction section 6 1 2 Requirements from environment and process Ambient temperature range Transmitter 40 to 60...

Страница 20: ...orted and fixed It is also advisable to mount the sensor and transmitter separately Information on the shock resistance of the measuring system 133 Information on the vibration resistance of the measu...

Страница 21: ...Torque wrench For wall mounting Open ended wrench for hexagonal screw max M5 For pipe mounting Open ended wrench AF 8 Phillips head screwdriver PH 2 For turning the transmitter housing compact versio...

Страница 22: ...seals nuts and washers can be ordered separately see Accessories section 124 5 1 2 3 4 A0018060 6 Mounting the sensor 1 Nut 2 Washer 3 Mounting bolts 4 Centering sleeve 5 Seal Arranging the mounting b...

Страница 23: ...se electrically conductive sealing compounds such as graphite Comply with the following instructions when installing seals Make sure that the seals do not protrude into the piping cross section For DI...

Страница 24: ...tightening torques mounting bolts and centering sleeves for ASME B16 5 Class 150 Nominal diameter Mounting bolts Length Centering sleeve Max screw tightening torque Nm lbf ft for a process flange with...

Страница 25: ...cal stress The transmitter of the remote version can be mounted in the following ways Wall mounting Pipe mounting Wall mounting 149 5 85 210 5 8 29 5 8 0 23 17 0 67 14 0 55 5 8 0 23 A0020523 7 Enginee...

Страница 26: ...eering unit mm in 6 2 5 Turning the transmitter housing To provide easier access to the connection compartment or display module the transmitter housing can be turned TX 20 4 x 1 2 P U S H T O R E M O...

Страница 27: ...ing torque 28 2 Open the housing cover 3 Unlock the display module 4 Remove the display module 5 Loosen the fixing screws of the smart sensor electronics module when reassembling pay attention to the...

Страница 28: ...of Aluminum Plastic 1 Housing cover 2 5 Nm 1 8 lbf ft 1 Nm 0 7 lbf ft 5 Smart sensor electronics module 0 6 Nm 0 4 lbf ft 7 Main electronics module 1 5 Nm 1 1 lbf ft 10 Transmitter housing 5 5 Nm 4 1...

Страница 29: ...0 7 lbf ft Reverse the procedure to reassemble the measuring device 6 3 Post installation check Is the device undamaged visual inspection Does the measuring device conform to the measuring point speci...

Страница 30: ...e customer must fulfill the following requirements Electrical safety In accordance with applicable federal national regulations Permitted temperature range 40 C 40 F to 80 C 176 F Minimum requirement...

Страница 31: ...on a Electrode cable b Coil current cable 1 Core 2 Core insulation 3 Core shield 4 Core jacket 5 Core reinforcement 6 Cable shield 7 Outer jacket Operation in zones of severe electrical interference T...

Страница 32: ...age Order code for Power supply Terminal numbers 1 L L 2 L N Option L wide range power unit AC100 to 240 V AC DC24 V Signal transmission 0 20 mA 4 20 mA HART with additional outputs and inputs Order c...

Страница 33: ...e version terminal assignment A Transmitter wall mount housing B Sensor connection housing 1 Electrode cable 2 Coil current cable n c Not connected insulated cable shields Terminal No and cable colors...

Страница 34: ...urrent cables insulate one core of the three core wire at the level of the core reinforcement You only require two cores for the connection Fit the fine wire cores with ferrules Transmitter Electrode...

Страница 35: ...Connecting the measuring device WARNING Risk of electric shock Components carry dangerous voltages Have electrical connection work carried out by correspondingly trained specialists only Observe appl...

Страница 36: ...ation When connecting the cable shielding to the ground terminal observe the grounding concept of the facility 6 Firmly tighten the cable glands 7 WARNING Housing degree of protection may be voided du...

Страница 37: ...ce with the terminal assignment 33 6 Firmly tighten the cable glands 7 WARNING Housing degree of protection may be voided due to insufficient sealing of the housing Screw in the screw without using an...

Страница 38: ...ntial Pay attention to internal grounding concepts in the company Pay attention to the pipe material or grounding Connection examples for standard situations Metal grounded pipe This connection method...

Страница 39: ...iner or pipe with electrically conductive liner Cathodic protection is integrated in the personal protection equipment Ground cable Copper wire at least6 mm2 0 0093 in2 A0017518 Prerequisite The senso...

Страница 40: ...degree of protection Type 4X enclosure To guarantee IP66 67 degree of protection Type 4X enclosure carry out the following steps after the electrical connection 1 Check that the housing seals are clea...

Страница 41: ...r connected to the right transmitter Check the serial number on the nameplate of the sensor and transmitter Does the supply voltage match the specifications on the transmitter nameplate 130 Is the ter...

Страница 42: ...verview of operation options 1 2 3 4 5 SC A0015607 1 Local operation via display module 2 Computer with Web browser e g Internet Explorer or with operating tool e g FieldCare AMS Device Manager SIMATI...

Страница 43: ...display Output Operating menu for experts Language Operatation Language Parameter 1 Setup Submenu 1 Submenu n Device tag Advanced setup Enter access code Parameter 1 Parameter n Submenu 1 Submenu n Di...

Страница 44: ...order option Extended HistoROM event messages that have occurred Device information submenu Contains information for identifying the device Measured values submenu Contains all current measured values...

Страница 45: ...lay Device tag 70 Status area Display area for measured values 4 line Operating elements 50 Status area The following symbols appear in the status area of the operational display at the top right Stat...

Страница 46: ...hree totalizers is displayed Output The measurement channel number indicates which of the outputs is displayed Status input Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The me...

Страница 47: ...for menu In the wizard Display symbol for wizard Omission symbol for operating menu levels in between Name of current Submenu Wizard Parameter Examples Display Display For more information about the...

Страница 48: ...agnostics menu Expert Appears In the menu next to the Expert selection At the left in the navigation path in the Expert menu Submenus wizards parameters Symbol Meaning Submenu Wizard Parameters within...

Страница 49: ...mask of the numeric and text editor Numeric editor Symbol Meaning 0 9 Selection of numbers from 0 to 9 Inserts decimal separator at the input position Inserts minus sign at the input position Confirm...

Страница 50: ...n one position to the left Deletes one character immediately to the left of the input position 8 3 4 Operating elements Key Meaning Minus key In a menu submenu Moves the selection bar upwards in a cho...

Страница 51: ...you to the next higher level If help text is open closes the help text of the parameter Pressing the key for 2 s returns you to the operational display home position With a Wizard Exits the wizard an...

Страница 52: ...52 Endress Hauser The context menu is closed and the operational display appears Calling up the menu via the context menu 1 Open the context menu 2 Press to navigate to the desired menu 3 Press to co...

Страница 53: ...0104 1 2 s 0091 1 0098 1 0098 1 0098 1 XXXX XXX X X 10 50 2800 Hz mA Display operat Display operat Setup Main menu English Main menu Format display Display Contrast display Display intervall 1 value m...

Страница 54: ...xample Input of 0914 Parameter Totalizer 1 If a different channel is jumped to Enter the direct access code with the corresponding channel number Example Input of 0914 2 Parameter Totalizer 2 For the...

Страница 55: ...IJK ABC 1x 001 FT 10 DEFG HIJK LMNO PQRS TUVW XYZ Aa1 ABC 001 FT 10 DEFG HIJK LMNO PQRS TUVW XYZ Aa1 ABC 001 FT 10 DEFG HIJK ABC A a 1 001 FT 10 DEFG HIJK ABC A a 1 001 FT 10 3456 789 Aa1 012 001 FT 1...

Страница 56: ...the user is currently logged on is indicated by the Access status display parameter Navigation path Operation Access status display 8 3 11 Disabling write protection via access code If the symbol app...

Страница 57: ...select the Keylock off option The keypad lock is switched off 8 4 Access to the operating menu via the Web browser 8 4 1 Function range Thanks to the integrated Web server the device can be operated a...

Страница 58: ...xcept 0 212 and 255 e g 192 168 1 213 Subnet mask 255 255 255 0 Default gateway 192 168 1 212 or leave cells empty 1 Switch on the measuring device and connect to the computer via the cable 61 2 If a...

Страница 59: ...e tag 70 Device status with status signal 109 Current measured values 98 Function row Functions Meaning Measured values The measured values of the device are displayed Menu Access to the operating men...

Страница 60: ...upload download 8 4 6 Disabling the Web server The Web server for the measuring device can enabled and disabled as required via the Web server functionality parameter Navigation Expert menu Communica...

Страница 61: ...LC 2 Field Communicator 475 3 Computer with operating tool e g FieldCare AMS Device Manager SIMATIC PDM 4 Commubox FXA195 USB 5 Field Xpert SFX350 or SFX370 6 VIATOR Bluetooth modem with connecting ca...

Страница 62: ...RJ45 61 Typical functions Configuring parameters of transmitters Loading and saving device data upload download Documentation of the measuring point Visualization of the measured value memory line rec...

Страница 63: ...eation 7 Navigation area with operating menu structure 8 Operating range 8 5 4 AMS Device Manager Function scope Program from Emerson Process Management for operating and configuring measuring devices...

Страница 64: ...T 64 Endress Hauser 8 5 6 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol Sourc...

Страница 65: ...vidual operating tools is listed in the table below along with information on where the file can be acquired Operating tool via HART protocol Sources for obtaining device descriptions Field Xpert SFX3...

Страница 66: ...ic variable Off Volume flow Mass flow Flow velocity Electronic temperature Measured variables for SV TV QV secondary tertiary and quaternary dynamic variable Volume flow Mass flow Electronic temperatu...

Страница 67: ...ed unit Command 48 option Read out the complete device diagnostics Command 1 Command 2 Command 3 Command 9 Command 33 Command 48 Command 2 Burst variable 0 Assignment of the individual HART variables...

Страница 68: ...st trigger level parameter Falling option The message is triggered if the specified measured value drops below the value in the Burst trigger level parameter On change option The message is triggered...

Страница 69: ...the operational display If nothing appears on the local display or a diagnostic message is displayed refer to the section on Diagnostics and troubleshooting 103 10 3 Setting the operating language Fa...

Страница 70: ...vice tag 70 Status input 71 Current output 1 72 Pulse frequency switch output 1 to 2 73 Display 80 Output conditioning 83 Low flow cut off 85 Empty pipe detection 87 HART input 82 Advanced setup 88 10...

Страница 71: ...he input The submenu only appears if the device was ordered with a status input Navigation Setup menu Status input Structure of the submenu Status input Assign status input Active level Response time...

Страница 72: ...g the particular current output Navigation Setup menu Current output 1 to 2 Structure of the wizard Volume flow Assign curr Mass flow Volume flow unit 4 20 mA NAMUR 4 20 mA US 4 20 mA Fixed current 0...

Страница 73: ...ment in Expert menu Unit choose list Country specific kg l lb ft Fixed density Enter fixed value for medium density 0 01 to 15 000 kg m 1 000 kg m Current span Select current range for process value o...

Страница 74: ...ng mode Parameter overview with brief description Parameter Description Selection User entry Factory setting Operating mode Define the output as a pulse frequency or switch output Pulse Frequency Swit...

Страница 75: ...fic kg l lb ft Fixed density Enter fixed value for medium density 0 01 to 15 000 kg m 1 000 kg m Value per pulse Enter measured value at which a pulse is output Signed floating point number 0 Pulse wi...

Страница 76: ...max freq Failure mode Failure freq Defined value Actual value 0 Hz A0023208 EN 25 Pulse frequency switch output 1 2 wizard in the Setup menu Frequency operating mode Parameter overview with brief desc...

Страница 77: ...requency value Enter minimum frequency 0 0 to 12 500 0 Hz 0 0 Hz Maximum frequency value Enter maximum frequency 0 0 to 12 500 0 Hz 12 500 0 Hz Measuring value at minimum frequency Enter measured valu...

Страница 78: ...he wizard for the switch output End of wizard Operating mode Switch Switch out funct Diag behavior Off On Assign diag beh Alarm Alarm or warning Warning Invert outp sig A0017439 EN 26 Pulse frequency...

Страница 79: ...sig Volume flow unit Mass flow unit A0023207 EN 27 Pulse frequency switch output 1 2 wizard in the Setup menu Switch operating mode Part 2 Parameter overview with brief description Parameter Descript...

Страница 80: ...low unit Result The selected unit applies for Output Low flow cut off Simulation process variable Unit choose list Country specific l h gal min us Unit totalizer Select process variable totalizer unit...

Страница 81: ...lay Select how measured values are shown on the display 1 value max size 1 bargraph 1 value 2 values 1 value large 2 values 4 values 1 value max size Value 1 display Select the measured value that is...

Страница 82: ...he measured value that is shown on the local display Picklist see 1st display value None 10 4 6 Configuring the HART input The HART input submenu contains all the parameters that must be configured fo...

Страница 83: ...Select command to read in external process variable Command 1 Command 3 Command 9 Command 33 Command 1 Slot number Define position of external process variable in burst command 1 to 4 1 Timeout Enter...

Страница 84: ...r pulse and frequency output Parameter overview with brief description Parameter Description User entry Selection Factory setting Display damping Set display reaction time to fluctuations in the measu...

Страница 85: ...ut Forward flow Forward Reverse flow Reverse flow Reverse flow compensation Forward flow 10 4 8 Configuring the low flow cut off The Low flow cut off wizard guides you systematically through all the p...

Страница 86: ...er Parameter Description Selection User entry Factory setting Off value low flow cutoff Enter off value for low flow cut off 0 to 100 0 50 Pressure shock suppression Enter time frame for signal suppre...

Страница 87: ...t EPD Off A0017210 EN 32 Empty pipe detection wizard in the Setup menu Parameter overview with brief description Parameter Description Selection User interface User entry Factory setting Empty pipe de...

Страница 88: ...rat Setup Diagnostic Display operat Setup Main menu English Main menu Status input Setup Setup Advanced setup Ent access code Advanced setup Def access code Device tag Language A0017519 EN 33 Using th...

Страница 89: ...t volume unit Result The selected unit is taken from Volume flow unit parameter Unit choose list Country specific l gal us Temperature unit Select temperature unit Result The selected unit applies for...

Страница 90: ...in arrow direction 10 5 3 Configuring the totalizer In the Totalizer 1 to 3 submenu the individual totalizers can be configured Navigation Setup menu Advanced setup Totalizer 1 to 3 Totalizer 1 to 3...

Страница 91: ...cal display Navigation Setup menu Advanced setup Display Structure of the submenu Display Format display Value 1 display 0 bargraph value 1 100 bargraph value 1 Decimal places 1 Value 2 display Decima...

Страница 92: ...umber of decimal places for the display value x x x x xx x xxx x xxxx x xx Value 2 display Select the measured value that is shown on the local display Picklist see 1st display value None Decimal plac...

Страница 93: ...header contents on local display Device tag Free text Device tag Header text Enter display header text Separator Select decimal separator for displaying numerical values Backlight Switch the local di...

Страница 94: ...he On option is selected in the Current output simulation parameter Enter the current value for simulation 3 59 3 to 22 5 3 mA 3 59 mA Frequency simulation 1 Switch simulation of the frequency output...

Страница 95: ...or the measuring device configuration are write protected and their values can no longer be changed Device access via the Web browser is protected as are the parameters for the measuring device config...

Страница 96: ...for 10 minutes the Web browser automatically returns to the login page The user role with which the user is currently logged on via the Web browser is indicated by the Access status tooling parameter...

Страница 97: ...ion view XXXX XXX X X 20 50 XX XX A0015870 If hardware write protection is disabled no option is displayed in the Locking status parameter 98 On the local display the symbol disappears from in front o...

Страница 98: ...nloading of data reset write access to the parameters is blocked for a short time Once the internal processing has been completed the parameters can be changed once again 11 2 Adjusting the operating...

Страница 99: ...Parameter Description User interface Factory setting Totalizer value 1 Displays the current totalizer counter value Signed floating point number 0 l Totalizer overflow 1 Displays the current totalizer...

Страница 100: ...rrent output 0 to 30 mA 0 mA Pulse output 1 Displays the value currently measured for the pulse output Positive floating point number 0 Hz Output frequency 1 Displays the value currently measured for...

Страница 101: ...enu Operation Control Totalizer Preset value Reset all totalizers Parameter overview with brief description Parameter Description Selection User entry Factory setting Control Totalizer Control totaliz...

Страница 102: ...al Clear logging data Parameter overview with brief description Parameter Description Selection User entry Factory setting Assign channel 1 Assign process variable to logging channel Off Volume flow M...

Страница 103: ...within the valid range Display is set too bright or too dark Set the display brighter by simultaneously pressing Set the display darker by simultaneously pressing Local display is dark but signal outp...

Страница 104: ...IT manager Not connecting to Web server Web server disabled Via the FieldCare operating tool check whether the Web server of the measuring device is enabled and enable it if necessary 60 No or incompl...

Страница 105: ...Color Meaning Flashing orange Activity present Communication Flashing white HART communication is active Alarm Green Measuring device is ok Flashing green Measuring device not configured Off Firmware...

Страница 106: ...at have occurred can be called up in the Diagnostics menu Via parameters 115 Via submenus 115 Status signals The status signals provide information on the state and reliability of the device by catego...

Страница 107: ...information The fault can be identified using the diagnostic information The short text helps you by providing information about the fault In addition the corresponding symbol for the diagnostic beha...

Страница 108: ...h diagnostic code 5 Operation time of occurrence 6 Remedial measures The user is in the diagnostic message 1 Press symbol The Diagnostic list submenu opens 2 Select the desired diagnostic event with o...

Страница 109: ...diagnostic event Symbol Meaning A0017271 Failure A device error has occurred The measured value is no longer valid A0017278 Function check The device is in service mode e g during a simulation A001727...

Страница 110: ...k C Status signal Device tag Device name Mass flow Volume flow Xxxxxxx 12 34 kg h 12 34 m h Xxxxxxx 1 2 3 A0021799 EN 1 Status area with status signal 106 2 Diagnostic information 107 3 Remedial measu...

Страница 111: ...ior submenu Expert menu System Diagnostic handling Diagnostic behavior A0014048 EN 36 Taking the example of the local display You can assign the following options to the diagnostic number as the diagn...

Страница 112: ...increase if the measuring device has one or more application packages In the case of some items of diagnostic information the status signal and the diagnostic behavior can be changed Adapt the diagnos...

Страница 113: ...nic failure 1 Reset device 2 Contact service F Alarm 311 Electronic failure 1 Do not reset device 2 Contact service M Warning 322 Electronic drift 1 Perform verification manually 2 Change electronic S...

Страница 114: ...rease system pressure F Alarm 530 Electrode cleaning is running 1 Check process cond 2 Increase system pressure C Warning 531 Empty pipe detection Execute EPD adjustment S Warning 537 Configuration 1...

Страница 115: ...f the submenu Diagnostics Actual diagnostics Previous diagnostics Parameter overview with brief description Parameter Prerequsite Description User interface Factory setting Actual diagnostics 1 diagno...

Страница 116: ...Config change I1157 Mem err ev list F311 Electr failure Eventlist 0d01h19m10s A0014008 EN 38 Illustrated using the example of the local display A maximum of 20 event messages can be displayed in chron...

Страница 117: ...89 Power on I1090 Configuration reset I1091 Configuration changed I1092 Trend data deleted I1110 Write protection switch changed I1137 Electronic changed I1151 History reset I1155 Reset electronic tem...

Страница 118: ...ivery settings Every parameter for which a customer specific default setting was ordered is reset to this customer specific value All other parameters are reset to the factory setting This option is n...

Страница 119: ...ation marks Extended order code 1 Displays the 1st part of the extended order code Character string Extended order code 2 Displays the 2nd part of the extended order code Character string Extended ord...

Страница 120: ...egrated HART input SD03 keypad lock Modification of SIL functionality HistoROM data logging in FieldCare HistoROM module Simulation of diagnostic events Ability to access Heartbeat Technology applicat...

Страница 121: ...e device 13 1 3 Replacing seals The sensor s seals particularly aseptic molded seals must be replaced periodically The interval between changes depends on the frequency of the cleaning cycles the clea...

Страница 122: ...into the W M life cycle management database 14 2 Spare parts Measuring device serial number Is located on the nameplate of the device Can be read out via the Serial number parameter in the Device info...

Страница 123: ...ng of the measuring device WARNING Danger to personnel and environment from fluids that are hazardous to health Ensure that the measuring device and all cavities are free of fluid residues that are ha...

Страница 124: ...15 2 Communication specific accessories Accessories Description Commubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface For details see Technical Informatio...

Страница 125: ...r your plant W M supports you with a wide range of software applications over the entire process from planning and procurement to the installation commissioning and operation of the measuring devices...

Страница 126: ...a transmitter and a sensor Two device versions are available Compact version the transmitter and sensor form a mechanical unit Remote version the transmitter and sensor are mounted separately from one...

Страница 127: ...ut signal External measured values Various pressure transmitters and temperature measuring devices can be ordered from Endress Hauser see Accessories section 125 It is recommended to read in external...

Страница 128: ...requency output With the order code for Output Input option I output 2 and 3 can be set as a pulse frequency or switch output Version Passive open collector Maximum input values DC 30 V 250 mA Voltage...

Страница 129: ...ows Current output 4 20 mA Failure mode Selectable as per NAMUR recommendation NE 43 Minimum value 3 6 mA Maximum value 22 mA Defined value 3 59 to 22 5 mA Actual value Last valid value 0 20 mA Failur...

Страница 130: ...ial measures Low flow cut off The switch points for low flow cut off are user selectable Galvanic isolation The following connections are galvanically isolated from each other Inputs Outputs Power sup...

Страница 131: ...5 mm2 20 to 14 AWG Electrode cable spring terminals for wire cross sections 0 5 to 2 5 mm2 20 to 14 AWG Coil current cable spring terminals for wire cross sections 0 5 to 2 5 mm2 20 to 14 AWG Sensor c...

Страница 132: ...0 A0003200 39 Maximum measured error in o r Accuracy of outputs o r of reading o f s of full scale value The outputs have the following base accuracy specifications Current output Accuracy Max 0 025...

Страница 133: ...en housing is open IP20 type 1 enclosure Sensor As standard IP66 67 type 4X enclosure Shock resistance Acceleration up to 2 g following IEC 60068 2 6 Vibration resistance Acceleration up to 2 g follow...

Страница 134: ...ssure loss No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter Pressure losses for configurations incorporating adapters according to DIN EN 545 20 System press...

Страница 135: ...ansmitter remote version Wall mount housing Depends on the material of the wall mount housing Polycarbonate plastic 1 3 kg 2 9 lb Aluminum AlSi10Mg coated 2 0 kg 4 4 lb Sensor remote version Weight da...

Страница 136: ...via the sensor housing ASME pressure rating Pressure rating Class 150 DN Mounting bolts Length internal diameter Centering sleeves Measuring tube mm in mm in mm in mm in 25 1 4 UNC 145 5 70 1 24 0 94...

Страница 137: ...ds 1 2 3 A0020640 40 Possible cable entries cable glands 1 Cable entry in transmitter housing wall mount housing or connection housing with internal thread M20 x 1 5 2 Cable gland M20 x 1 5 3 Adapter...

Страница 138: ...using option N Remote polycarbonate or option P Remote coated aluminum The various cable entries are suitable for hazardous and non hazardous areas Electrical connection Material Cable gland M20 1 5 N...

Страница 139: ...tches to red in event of device errors Format for displaying measured variables and status variables can be individually configured Permitted ambient temperature for the display 20 to 50 C 4 to 122 F...

Страница 140: ...4 Commubox FXA195 USB 5 Field Xpert SFX350 or SFX370 6 VIATOR Bluetooth modem with connecting cable 7 Transmitter Service interface Service interface CDI RJ45 HART 1 3 2 A0020481 1 Computer with Web...

Страница 141: ...ertified for use in hazardous areas and the relevant safety instructions are provided in the separate Control Drawing document Reference is made to this document on the nameplate Drinking water approv...

Страница 142: ...m 20 message entries basic version to up to 100 entries Data logging line recorder Memory capacity for up to 1000 measured values is activated 250 measured values can be output via each of the 4 memor...

Страница 143: ...ations App Enter the serial number from the nameplate or scan the 2 D matrix code QR code on the nameplate Standard documentation Brief Operating Instructions Measuring device Documentation code Proma...

Страница 144: ...the parameter can be found in the manual 17 1 1 Main menu Main menu Display language 69 Operation 144 Setup 145 Diagnostics 149 Expert 153 17 1 2 Operation menu Operation Display language 69 Web serv...

Страница 145: ...ut 73 Mass flow unit 73 Volume flow unit 73 Current span 73 0 4 mA value 73 20 mA value 73 20 mA value 73 0 4 mA value 73 Failure mode 73 Failure current 73 Pulse frequency switch output 1 to 2 73 Ope...

Страница 146: ...um frequency value 77 Maximum frequency value 77 Minimum frequency value 77 Measuring value at minimum frequency 77 Measuring value at maximum frequency 77 Measuring value at maximum frequency 77 Meas...

Страница 147: ...ay damping 84 Assign current output 73 Damping output 1 84 Measuring mode output 1 85 Assign frequency output 76 Damping output 1 84 Measuring mode output 1 85 Assign pulse output 74 Measuring mode ou...

Страница 148: ...e mode 83 Device ID 83 Device type 83 Manufacturer ID 83 Burst command 83 Slot number 83 Timeout 83 Failure mode 83 Failure value 83 Advanced setup 88 Enter access code 95 System units 89 Volume flow...

Страница 149: ...l places 2 92 Value 3 display 82 0 bargraph value 3 82 100 bargraph value 3 82 Decimal places 3 92 Value 4 display 82 Decimal places 4 92 Display language 93 Display interval 93 Display damping 93 Hea...

Страница 150: ...Device tag 119 Serial number 119 Firmware version 119 Device name 119 Order code 119 Extended order code 1 to 3 119 ENP version 119 Device revision 119 Device ID 119 Device type 119 Manufacturer ID 11...

Страница 151: ...requency 2 100 Pulse output 2 100 Switch status 2 100 Data logging 1 101 Assign channel 1 to 4 102 Logging interval 102 Clear logging data 102 Heartbeat 2 143 Performing verification Year Month Day Ho...

Страница 152: ...rence electrode potential against PE Simulation 93 Assign simulation process variable 94 Value process variable 94 Simulation status input 94 Input signal level 94 Simulation current output 1 94 Value...

Страница 153: ...ert menu 153 with its submenus and parameters The direct access code to the parameter is given in brackets The page reference indicates where a description of the parameter can be found in the manual...

Страница 154: ...mal places 4 0119 92 Display interval 0096 93 Display damping 0094 93 Header 0097 93 Header text 0112 93 Separator 0101 93 Contrast display 0105 Backlight 0111 93 Access status display 0091 Diagnostic...

Страница 155: ...n Define access code 95 Define access code 0093 95 Confirm access code 95 Device reset 0000 118 Activate SW option 0029 Software option overview 0015 Sensor submenu Sensor Measured values 98 Process v...

Страница 156: ...ume flow unit 0553 73 Volume unit 0563 74 Temperature unit 0557 89 Mass flow unit 0554 73 Mass unit 0574 74 Density unit 0555 73 Date time format 2812 User specific units User volume text 0567 User vo...

Страница 157: ...859 87 Empty pipe adjust value 6527 Full pipe adjust value 6548 Measured value EPD 6559 Empty pipe adjust New adjustment 6560 87 Progress 6571 87 External compensation External value 6707 External den...

Страница 158: ...se time status input 1354 71 Output submenu Output Current output 1 72 Assign current output 0359 73 Current span 0353 73 Fixed current 0365 0 4 mA value 0367 73 20 mA value 0372 73 Measuring mode 035...

Страница 159: ...g value at minimum frequency 0476 77 Measuring value at maximum frequency 0475 77 Measuring mode 0479 Damping output 84 Response time 0491 Failure mode 0451 77 Failure frequency 0474 77 Output frequen...

Страница 160: ...ype 7008 83 Manufacturer ID 7009 83 Burst command 7006 83 Slot number 7010 83 Timeout 7005 83 Failure mode 7011 83 Failure value 7012 83 Input Value 7003 Status 7004 HART output 65 Configuration HART...

Страница 161: ...118 Device revision 0204 119 Device ID 0221 119 Device type 0222 119 Manufacturer ID 0223 119 HART revision 0205 65 HART descriptor 0212 HART message 0216 Hardware revision 0206 Software revision 0224...

Страница 162: ...event category Event category 004 0262 Event category 441 0210 Event category 442 0230 Event category 443 0231 Event category 531 0261 Event category 832 0218 Event category 833 0225 Event category 8...

Страница 163: ...ation text User concentration factor User concentration offset A 0 A 1 to 4 B 1 to 3 Diagnostics submenu Diagnostics 103 Actual diagnostics 0691 115 Previous diagnostics 0690 115 Operating time from r...

Страница 164: ...eway 7210 120 Data logging 1 101 Assign channel 1 to 4 0851 1 to 4 102 Logging interval 0856 102 Clear logging data 0855 102 Min max values Reset min max values 6151 Main electronic temperature Minimu...

Страница 165: ...s 12103 Overall result 12149 Verification results Date time 12142 Verification ID 12141 Operating time 12126 Overall result 12149 Sensor 12152 Sensor electronic module 12151 I O module 12145 Monitorin...

Страница 166: ...2 0459 1 to 2 94 Switch output simulation 1 to 2 0462 1 to 2 94 Switch status 1 to 2 0463 1 to 2 94 Simulation device alarm 0654 94 Diagnostic event category 0738 95 Simulation diagnostic event 0737 9...

Страница 167: ...eclaration of Conformity 10 Define access code 95 96 Degree of protection 40 133 Design Measuring device 12 Designated use 9 Device components 12 Device description files 65 Device documentation Suppl...

Страница 168: ...n check 69 Function scope AMS Device Manager 63 Field Communicator 64 Field Communicator 475 64 Field Xpert 62 SIMATIC PDM 63 Functions see Parameter G Galvanic isolation 130 H Hardware write protecti...

Страница 169: ...Sensor 15 Transmitter 14 Navigation path navigation view 47 Navigation view In the submenu 47 In the wizard 47 Numeric editor 49 O Operable flow range 127 Operating elements 50 107 Operating keys see...

Страница 170: ...ocess conditions 100 Advanced display configurations 91 Current output 72 Device reset 118 Device tag 70 Empty pipe detection EPD 87 HART input 82 Local display 80 Low flow cut off 85 Operating langua...

Страница 171: ...the signal cables 36 Turning the display module 28 Turning the housing 26 Transporting the measuring device 16 Troubleshooting General 103 Turning the display module 28 Turning the electronics housing...

Страница 172: ...www addresses endress com...