Micropilot M FMR250 FOUNDATION Fieldbus
Commissioning
Hauser
57
6.4.3
Envelope curve
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("
envelope curve
"
(0E)
function group) is recommended.
Function "plot settings" (0E1)
Select which information will be displayed in the LCD:
•
envelope curve
• env.curve+FAC (on FAC see BA291F/00/EN)
• env.curve+cust.map (i.e. customer tank map is also displayed)
Function "recording curve" (0E2)
This function defines whether the envelope curve is read as a
•
single curve
or
• cyclic.
!
Note!
• If the cyclical envelope curve is active in the display, the measured value is refreshed in a slower
cycle time. It is therefore recommended to exit the envelope curve display after optimising the
measuring point.
• An
orientation
of the Micropilot can help to optimise measurement in applications with very
weak level echos or strong interference echos by increasing the useful echo/reducing the
interference echo (see "Orientation of the Micropilot",
→
ä
84).
⇒
E HAUSER
E
+
–
⇒
E HAUSER
E
+
–