Commissioning
Micropilot M FMR250 FOUNDATION Fieldbus
52
Hauser
Function "process cond." (00C), solids only
This function is used to select the process conditions.
Selection:
•
standard
• fast change
• slow change
• test:no filter
Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (=zero).
L00-FMR2xxxx-14-00-06-en-008
"
Caution!
For dish bottoms or conical outlets, the zero point should be no lower than the point at which the
radar beam hits the bottom of the tank.
⇒
E HAUSER
E
+
–
⇒