Commissioning
Micropilot M FMR250 FOUNDATION Fieldbus
66
Hauser
3.
Open the FOUNDATION Fieldbus method "basic setup":
FMR2xx-FF-Methode-in-NIConfig
4.
The method contains the following parameters
3)
:
a. Application parameters (
→
ä
48)
– PARMEDIATYPE (media type)
With the selection "liquid" only the following application parameters can be
adjusted:
– PARTANKSHAPE (tank shape)
– PARDIELECTRICCONSTANT (medium property)
– PARPROCESSCONDITION (process cond.)
With the selection "solid" only the following application parameters can be
adjusted:
– PARVESSELSILO (vessel / silo)
– PARDIELECTRICCONSTANT (medium property)
– PARPROCESSPROPERTIES (process propert.)
b. Empty and full calibration (
→
ä
52)
– PAREMPTYCALIBRATION (empty calibration)
– PARFULlCALIBRATION (full calibration)
c. Interference echo suppression (
→
ä
54)
– PARCHECKDISTANCE (check distance)
– PARSUPPRESSIONDISTANCE (range of mapping)
– PARSTARTMAPPINGRECORD (start maping)
– PARPRESMAPRANGE (pres. map. dist.)
– PARCUSTTANKMAP (cust. tank map)
3)
In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display:
- parameter names (e.g. "PARTANKSHAPE")
- label texts (e.g. "tank shape")