Appendix
Micropilot M FMR250 FOUNDATION Fieldbus
112
Hauser
11.7.9
Simulation
The SIMULATE parameter allows the Sensor block output value to be simulated, provided
simulation has also been enabled at the device DIP switch. The simulation must be enabled, a value
and/or status entered and the block must be in AUTO mode. During simulation the Sensor output
value is substituted by the simulated value.
A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT.
Parameter
Description
SIMULATE
Enables, sets and displays a simulated value, options:
– enable/disable
– simulated value
– output value