Micropilot M FMR250 FOUNDATION Fieldbus
Commissioning
Hauser
47
6.4
Commissioning by the display and operatig module
6.4.1
Power up instrument
The
"Basic setup" (00)
function group lists all the functions which are required for a standard
measurement task to commission the Micropilot M. When you have completed your input for a
function, the next function appears automatically. In this way, you are guided through the complete
calibration.
After switching on the supply voltage, the
instrument is first initialised.
L00-fmp-fxxx-20-00-00-en-003
Then the following appear for approximately
five seconds:
• Device type
• Software version
• Type of digital communication signal
Press
F
to exit this display.
L00-fmr-fxxx-20-00-00-en-103
On first power-up, you are requested to select
the language for the display texts.
L00-fmrxf092-20-00-00-en-001
Then you are requested to select the unit of
length for your measurements.
L00-fmrxf0c5-20-00-00-en-001
A measured value is displayed. This is NOT
equivalent to the level in your tank. Firstly carry
out a basic calibration.
L00-fmrxf000-20-00-00-en-001
Press
F
to switch to the group selection.
Press
F
again to start the basic calibration.
L00-fmrxfg00-20-00-00-en-001