Cerabar PMP71B HART
Technical data
Hauser
73
Process connection and process adapter when using the separate housing
FEP cable
• IP69 (on sensor side)
• IP66 TYPE 4/6P
• IP68 (1.83 mH
2
O for 24 h) TYPE 4/6P
PE cable
• IP69 (on sensor side)
• IP66 TYPE 4/6P
• IP68 (1.83 mH
2
O for 24 h) TYPE 4/6P
Vibration resistance
Single compartment housing
Mechanical construction
Sine wave oscillation IEC 61298-3:2008 Shock
Measuring device
10 Hz to 60 Hz: ±0.35 mm (0.0138 in)
60 Hz to 1000 Hz: 5 g
30 g
Measuring device with "Compact" or "Temperature isolator"
diaphragm seal type
10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 1000 Hz: 2 g
30 g
1)
For applications with very high temperatures, either a measuring device with a temperature isolator or
with a capillary can be used. If vibrations also occur in the application, Hauser recommends using
a measuring device with a capillary. If a measuring device with a temperature isolator or capillary is used, it
must be mounted with a mounting bracket.
Aluminum dual compartment housing
Mechanical construction
Sine wave oscillation IEC 61298-3:2008 Shock
Measuring device
10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 1000 Hz: 2 g
30 g
Measuring device with "Compact" or "Temperature isolator"
diaphragm seal type
10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 1000 Hz: 2 g
30 g
1)
For applications with very high temperatures, either a measuring device with a temperature isolator or
with a capillary can be used. If vibrations also occur in the application, Hauser recommends using
a measuring device with a capillary. If a measuring device with a temperature isolator or capillary is used, it
must be mounted with a mounting bracket.
Stainless steel dual compartment housing
Mechanical construction
Sine wave oscillation IEC 61298-3:2008 Shock
Measuring device
10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 1000 Hz: 2 g
15 g
Measuring device with "Compact" or "Temperature isolator"
diaphragm seal type
10 Hz to 150 Hz: 0.2 g
15 g
1)
For applications with very high temperatures, either a measuring device with a temperature isolator or
with a capillary can be used. If vibrations also occur in the application, Hauser recommends using
a measuring device with a capillary. If a measuring device with a temperature isolator or capillary is used, it
must be mounted with a mounting bracket.
Electromagnetic
compatibility (EMC)
• Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation
EMC (NE21)
• With regard to the safety function (SIL), the requirements of EN 61326-3-x are satisfied
• Maximum deviation with interference influence: < 0.5% of span with full measuring
range (TD 1:1)