Electrical connection
Cerabar PMP71B HART
28
Hauser
6.2.2
Terminals
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm
2
(20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm
2
(20 to 12 AWG)
6.2.3
Cable specification
• Protective ground or grounding of the cable shield: rated cross-section > 1 mm
2
(17
AWG)
Rated cross-section of 0.5 mm
2
(20 AWG) to 2.5 mm
2
(13 AWG)
• Cable outer diameter: Ø5 to 12 mm (0.2 to 0.47 in) depends on the cable gland used
(see the Technical Information)
6.2.4
4-20 mA HART
2
3
4
Y
+
+
-
-
I
1
mA
A0028908
2
Block diagram of HART connection
1
Measuring device with HART communication
2
HART communication resistor
3
Power supply
4
Manometer
The HART communication resistor of 250 Ω in the signal line is always necessary in
the case of a low-impedance power supply.
Take the voltage drop into consideration:
Maximum 6 V for a 250 Ω communication resistor
6.2.5
Overvoltage protection
Devices without optional overvoltage protection
Equipment from Hauser fulfills the requirements of the product standard IEC /
DIN EN 61326-1 (Table 2 Industrial Environment).
Depending on the type of port (DC power supply, input/output port) different testing levels
according to IEC / DIN EN 61326-1 against transient overvoltages (Surge) are applied
(IEC / DIN EN 61000-4-5 Surge):
Test level on DC power ports and input / output ports is 1000 V line to earth
Devices with optional overvoltage protection
• Spark-over voltage: min. 400 V DC
• Tested according to IEC / DIN EN 60079-14 sub chapter 12.3 (IEC / DIN EN 60060-1
chapter 7)
• Nominal discharge current: 10 kA
Overvoltage category
Overvoltage category II