Technical data
Cerabar PMP71B HART
68
Hauser
15
Technical data
15.1 Output
Output signal
Current output
4 to 20 mA with superimposed digital communication protocol HART, 2-wire
The current output offers a choice of three different operating modes:
• 4.0 to 20.5 mA
• NAMUR NE 43: 3.8 to 20.5 mA (factory setting)
• US mode: 3.9 to 20.8 mA
Signal on alarm
Signal on alarm in accordance with NAMUR recommendation NE 43.
Options:
• Max alarm: can be set from 21.5 to 23 mA
• Min. alarm: < 3.6 mA (factory setting)
Load
4 to 20 mA HART
U – 10.5 V
23 mA
[ ]
W
10.5
35
30
1065
848
£
U
[V]
1
2
RLmax
3
R Lmax
A0039232
1
Power supply 10.5 to 30 VDC Ex i
2
Power supply 10.5 to 35 VDC, for other types of protection and for non-certified device versions
3
R
Lmax
maximum load resistance
U
Supply voltage
Operation via handheld terminal or PC with operating program: take minimum
communication resistance of 250 Ω into consideration.
Damping
A damping affects all outputs (output signal, display). Damping can be enabled as follows:
• Via the onsite display, Bluetooth, handheld terminal or PC with operating program,
continuous from 0 to 999 seconds
• Factory setting: 1 s
Ex connection data
See the separate technical documentation (Safety Instructions (XA)) on
www.endress.com/download
.