Commissioning
Cerabar PMP71B HART
48
Hauser
9.9.3
Software locking or unlocking
If operation is locked by means of the DIP switch, you can only unlock operation again
by means of the DIP switch.
Locking via password in FieldCare / DeviceCare / SmartBlue
Access to the configuration of the measuring device can be locked by assigning a
password. When the device is delivered from the factory, the user role is set to the
Maintenance
option. The measuring device can be fully configured with the
Maintenance
option user role. Afterwards, access to the configuration can be locked by assigning a
password. The
Maintenance
option switches to the
Operator
option as a result of the
locking. The configuration can be accessed by entering the password.
The password is defined under:
System
menu
User management
submenu
The user role is changed from the
Maintenance
option to the
Operator
option under:
System → User management
Deactivating the lock via FieldCare / DeviceCare / SmartBlue
After entering the password, you can enable the configuration of the measuring device as
an
Operator
option with the password. The user role then changes to
Maintenance
option.
If necessary, the password can be deleted in the
User management
submenu: System
→ User management