Deltabar PMD75B HART
Installation
Hauser
17
5.2.2
Level measurement
Level measurement in open vessels
–
+
min.
p
atm
4
5
p
atm
2
3
6
1
A0038215
1
Measuring device
2
Three-valve manifold
3
The low-pressure side is open to atmospheric pressure
4
Drain valve
5
Separator
6
Shutoff valve
• Mount the measuring device below the lower measuring connection so that the piping is
always filled with liquid
• The low-pressure side is open to atmospheric pressure
• When measuring in media with solid parts, such as dirty liquids, installing separators
and drain valves is useful for capturing and removing sediment
Level measurement in a closed vessel
–
+
min.
5
4
2
1
3
–
max.
A0038217
1
Shutoff valve
2
Measuring device
3
Three-valve manifold
4
Separator
5
Drain valves
• Mount the measuring device below the lower measuring connection so that the piping is
always filled with liquid
• Always connect the low-pressure side above the maximum level
• When measuring in media with solid parts, such as dirty liquids, installing separators
and drain valves is useful for capturing and removing sediment