Deltabar PMD75B HART
Commissioning
Hauser
41
9.7.3
Outputting of the pressure value at the current output
Pressure and temperature units are converted automatically. Other units are not
converted.
In the following example, the pressure value should be measured in a tank and output on
the current output. The maximum pressure of 450 mbar (6.75 psi) corresponds to the 20
mA current. The 4 mA current corresponds to a pressure of 50 mbar (0.75 psi).
Prerequisites:
• Measured variable in direct proportion to the pressure
• Due to the orientation of the measuring device, there may be pressure shifts in the
measured value (when the vessel is empty or partly filled, the measured value is not
zero)
Perform a position adjustment if necessary
• The pressure profile must be linear (
SV - Transfer function
parameter =
Linear
option
Display: Under
Guidance
menu
Commissioning
wizard, keep pressing the key until
the
Assign PV
parameter is reached. Press the key to confirm. Select the scaled
variable and press the key to confirm.
FieldCare:
Guidance
menu
Commissioning
wizard Press the
Start
option, then press
again until the SV and PV values can be configured.
• In the
Assign PV
parameter, the
Pressure
option must be set (factory setting)
Display: In the
Guidance
menu
Commissioning
wizard, keep pressing the key until
the
Assign PV
parameter is reached. Confirm with the key, select the
Pressure
option
and press the key to confirm.
FieldCare: The PV value can also be modified in the
Application
menu
Scaled variable
parameter.
B
450 mbar
20 mA
A
50 mbar
4 mA
I
[mA]
20
4
50
p
[mbar]
450
–
+
+ -
A0039093
A
Lower range value output
B
Upper range value output
Adjustment:
1. Enter the pressure value for the 4 mA current via the
Lower range value output
parameter (50 mbar (0.75 psi)).
Menu path: Guidance → Commissioning → Lower range value output
2. Enter the pressure value for the 20 mA current via the
Upper range value output
parameter (450 mbar (6.75 psi))
Menu path: Guidance → Commissioning → Upper range value output
Result: The measuring range is set to 4 to 20 mA.