Diagnostics and troubleshooting
Deltabar PMD75B HART
56
Hauser
11.1.3 Additional tests
If no clear cause of the error can be identified or the source of the problem can be both the
device and the application, the following additional tests can be performed:
1. Switch on the simulation – see if current output of device is ok.
2. Dismount affected device and perform a bench-test (is the device working properly?)
3. Replace the affected device with a functioning device. Does the problem persist or is
the measuring point the source of the problem?