Operation options
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
24
Hauser
7
Operation options
7.1
Operation with an operating menu
7.1.1
IO-Link
IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device
and an IO-Link master. The measuring device features an IO-Link communication interface
type 2 with a second IO function on pin 4. This requires an IO-Link-compatible assembly
(IO-Link master) for operation. The IO-Link communication interface enables direct access
to the process and diagnostic data. It also provides the option of configuring the measuring
device on the fly.
Physical layer, the measuring device supports the following features:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition (supports minimum scope of IdentClass)
• SIO mode: yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 2.5 msec.
• Process data width: 32 bit
• IO-Link data storage: yes
• Block parameterization: yes
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type.
• Select "Device Driver" as the software type.
Select IO-Link (IODD).
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by
– Manufacturer
– Article number
– Product type
7.1.2
Operating concept
Operation with an operating menu is based on an operation concept with "user roles" .
User role
Meaning
Operator
(display level)
Operators are responsible for the devices during normal "operation". This is usually limited to
reading process values either directly at the device or in a control room. Should an error occur,
these users simply forward the information on the errors but do not intervene themselves.
Maintenance
(user level)
Service engineers usually work with the devices in the phases following device commissioning.
They are primarily involved in maintenance and troubleshooting activities for which simple
settings have to be made on the device. Technicians work with the devices over the entire life
cycle of the product. Thus, commissioning and advanced settings and configurations are some
of the tasks they have to carry out.
Содержание Ceraphant PTP31B
Страница 92: ...www addresses endress com 71422361 71422361...