Electrical connection
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
22
Hauser
6.1.2
Supply voltage
Supply voltage IO-Link: 10 to 30 V DC at a DC power unit
IO-Link communication is guaranteed only if the supply voltage is at least 18 V.
6.1.3
Current consumption and alarm signal
Intrinsic power consumption
Alarm current (for devices with analog output)
≤ 60 mA
≥21 mA (factory setting)
Maximum current consumption: ≤ 300 mA
1)
Setting min. alarm current ≤3.6mA can be ordered via the product order structure. Min. alarm current
≤3.6mA can be configured at the device or via IO-Link.
6.2
Switching capacity
• Switch state ON
a
≤ 200 mA
a
≤100 μA
• Switch cycles: >10,000,000
• Voltage drop PNP: ≤2 V
• Overload protection: Automatic load testing of switching current;
– Max. capacitive load: 1 μF at max. supply voltage (without resistive load)
– Max. cycle duration: 0.5 s; min. t
on
: 40 μs
– Periodic disconnection from protective circuit in the event of overcurrent (f = 2 Hz) and
"F804" displayed
6.3
Connection data
6.3.1
Load (for devices with analog output)
In order to guarantee sufficient terminal voltage, a maximum load resistance R
L
(including
line resistance) must not be exceeded depending on the supply voltage U
B
of the supply
unit.
The maximum load resistance depends on the terminal voltage and is calculated according
to the following formula:
1)
100 mA can be guaranteed over the entire temperature range for the switch outputs "2 x PNP" and "1 x PNP + 4 to 20 mA output". For lower
ambient temperatures, higher currents are possible but cannot be guaranteed. Typical value at 20 °C (68 °F) approx. 200 mA. 200 mA can be
guaranteed over the entire temperature range for the "1 x PNP" current output.
2)
Larger currents are supported, thus deviating from the IO-Link standard.