Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Installation
Hauser
19
A0025923
5.5
Mounting instructions for oxygen applications
Oxygen and other gases can react explosively to oils, grease and plastics, such that, among
other things, the following precautions must be taken:
• All components of the system, such as measuring devices, must be cleaned in accordance
with the BAM requirements.
• Dependent on the materials used, a certain maximum temperature and a maximum
pressure for oxygen applications must not be exceeded.
• The following table lists devices (devices only, not accessories or enclosed accessories),
which are suitable for gaseous oxygen applications.
Device
p
max
for oxygen applications
T
max
for oxygen applications
Option
PTC31B
40 bar (600 psi)
–10 to +60 °C (+14 to +140 °F)
HB
1)
Product Configurator, order code for "Service"
5.6
Post-installation check
Is the device undamaged (visual inspection)?
Does the device comply with the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature range
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected against precipitation and direct sunlight?
Are the securing screws tightened securely?
Is the pressure compensation element pointing downwards at an angle or to the side?
To prevent moisture from penetrating, ensure that the connecting cables/plugs are pointing downwards.