Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Description of device parameters
Hauser
69
Note
The switching delay time/switchback delay time function is implemented using the
dS2
and
dR2
parameters. Since the parameter settings depend on one another, the parameters
are described all together.
• dS2 = switching delay time, output 2
• dR2 = switchback delay time, output 2
Navigation
Display: EF → Switching delay.../Switchback delay...
IO-Link: Parameter → Application → Switch output (OU2) → Switching delay.../Switchback
delay...
Description
To prevent switch-on and switch-off if values are around the switch point "SP2" or the
switchback point "RP2", a delay in a range of 0 – 50 seconds, to two decimal places, can be
set for the individual points.
If the measured value leaves the switching range during the delay time, the delay time
starts again from scratch.
Example
• SP2 = 2 bar (29 psi)
• RP2 = 1 bar (14.5 psi)
• dS2 = 5 seconds
• dR2 = 2 seconds
dS2/: ≥2 bar (29 psi) must be present for at least 5 seconds for SP2 to become active.
dR2/: ≥1 bar (14.5 psi) must be present for at least 2 seconds for RP2 to become active.
2
1
0
SP2
RP2
dS2
dS2
dR2
0
HNO
p
t
1
HNC
A0037013
0
0-signal. Output open in quiescent state.
1
1-signal. Output closed in quiescent state.
2
Hysteresis (difference between the value of the switch point "SP2" and the value of the switchback point "RP2")
HNO NO contact
HNC NC contact
SP2 Switch point 2
RP2 Switchback point 2
dS2 Set time for which the specific switch point must be reached continuously without interruption until an
electrical signal change takes place.
dR2 Set time for which the specific switchback point must be reached continuously without interruption until an
electrical signal change takes place.
Input range
0.00 - 50.00 seconds
Factory setting
0