Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Overview of the onsite display operating menu
Hauser
51
13
Overview of the onsite display operating menu
Depending on the parameter configuration, not all submenus and parameters are
available. Information on this can be found in the parameter description under
"Prerequisite".
Switch output
Level
0
Level
1
Level
2
Level
3
Description
Details
1 x PNP
2 x PNP
1 x PNP +
4-20 mA
KYL
If "KYL" is shown on the display, this means that the keys of the device are locked.
To unlock the keys, see → 28
SP1
Switch point value, output 1
RP1
Switchback point value, output 1
FH1
Upper value for pressure window, output 1
FL1
Lower value for pressure window, output 1
B
SP2
Switch point, output 2
B
RP2
Switchback point, output 2
B
FH2
Upper value for pressure window, output 2
B
FL2
Lower value for pressure window, output 2
A
STL
Value for 4 mA (LRV)
A
STU
Value for 20 mA (URV)
EF
FUNC
Extended functions
OFF
-
I
-
PNP
-
UNI
BAR
Unit bar
-
KPA
Unit kPa (depends on the sensor measuring range)
-
MPA
Unit MPa (depends on the sensor measuring range)
-
PSI
Unit psi
-
ZRO
Zero point configuration
GTZ
Zero point adoption
TAU
Damping
A
I
Current output
-
GTL
Pressure applied for 4mA (LRV)
GTU
Pressure applied for 20mA (URV)
FCU
Alarm current
A
MIN
In the event of an error: MIN (≤3.6 mA)
-
A
MAX
In the event of an error: MAX (≥21 mA)
-
A
HLD
Last current value (HOLD)
-
dS1
Switching delay time, output 1
dR1
Switchback delay time, output 1
Ou1
Output 1
-
HNO
NO contact for hysteresis function
HNC
NC contact for hysteresis function