Description of device parameters
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
58
Hauser
Simulation Switch Output (OU2)
Simulation output 2 (for devices with 2 switch outputs)
Navigation
Display: DIAG → Simulation Switch Output (OU2)
IO-Link: Diagnosis → Simulation Switch Output (OU2)
Description
Switch output simulation.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A visual warning is indicated on the local display
(C485 - Simulation Active). The simulation must be ended actively via the menu. If the
device is disconnected from the power supply during the simulation and then power is
resupplied afterwards, the simulation mode is not resumed, and instead the device
continues operation in the measuring mode.
Options
• OFF
• OPN (switch output open)
• CLS (switch output closed)
Operating Mode (FUNC)
Navigation
Display: EF → Operating Mode (FUNC)
IO-Link: Parameter → Application → Sensor → Operating Mode (FUNC)
Description
Enables the desired behavior of output 2 (not IO-Link output)
Options
Options:
• OFF
• 4-20 mA (I) ((can only be selected if the device has been ordered with 4-20mA))
• DC-PNP (PNP)
Unit changeover (UNI)
Navigation
Display: EF → Unit changeover (UNI)
IO-Link: Parameter → Application → Sensor → Unit changeover (UNI)
Description
Select the pressure engineering unit. If a new pressure engineering unit is selected, all
pressure-specific parameters are converted.
Options
• bar
• kPa
• Mpa
• psi
Factory setting
Depends on order specifications.
Zero point configuration (ZRO)