Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 10
Unidrive SP Advanced User Guide
185
Issue Number: 10 www.controltechniques.com
Et
External trip from input on terminal 31
6
Check terminal 31 signal
Check value of Pr
10.32
Enter 12001 in Pr
xx.00
and check for parameter controlling Pr
10.32
Ensure Pr
10.32
or Pr
10.38
(=6) are not being controlled by serial comms
HF01
Data processing error: CPU address error
Hardware fault - return drive to supplier
HF02
Data processing error: DMAC address error
Hardware fault - return drive to supplier
HF03
Data processing error: Illegal instruction
Hardware fault - return drive to supplier
HF04
Data processing error: Illegal slot instruction
Hardware fault - return drive to supplier
HF05
Data processing error: Undefined exception
Hardware fault - return drive to supplier
HF06
Data processing error: Reserved exception
Hardware fault - return drive to supplier
HF07
Data processing error: Watchdog failure
Hardware fault - return drive to supplier
HF08
Data processing error: Level 4 crash
Hardware fault - return drive to supplier
HF09
Data processing error: Heap overflow
Hardware fault - return drive to supplier
HF10
Data processing error: Router error
Hardware fault - return drive to supplier
HF11
Data processing error: Access to EEPROM failed
Hardware fault - return drive to supplier
HF12
Data processing error: Main program stack overflow
Hardware fault - return drive to supplier
HF13
Data processing error: Software incompatible with hardware
Hardware or software fault - return drive to supplier
HF17
Multi-module system thermistor short circuit or open circuit
217
Hardware fault - return drive to supplier
HF18
Multi-module system interconnect cable error
218
Parallel cable in wrong port. (Note in multi module systems, the drive with the trip code displayed indicates that the next drive in the
sequence has the physical fault)
Hardware fault - return drive to supplier
HF19
Temperature feedback multiplexing failure
219
Hardware fault - return drive to supplier
HF20
Power stage recognition: serial code error
220
Hardware fault - return drive to supplier
HF21
Power stage recognition: unrecognised frame size
221
Hardware fault - return drive to supplier
HF22
Power stage recognition: multi module frame size mismatch
222
Hardware fault - return drive to supplier
HF23
Power stage recognition: multi module voltage or current rating mismatch
223
Hardware fault - return drive to supplier
HF24
Power stage recognition: unrecognised drive size
224
Hardware fault - return drive to supplier
Trip