Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 8
Unidrive SP Advanced User Guide
169
Issue Number: 10 www.controltechniques.com
OFF (0) = Terminal is an input
On (1) = Terminal is an output
When this parameter is 0, Pr
8.25
and Pr
8.26
are set up automatically according to the setting of the reference select Pr
1.14
. Setting this parameter
to 1 disables this function.
This parameter has no effect in Regen mode.
8.31
T24 digital I/O 1 output select
8.32
T25 digital I/O 2 output select
8.33
T26 digital I/O 3 output select
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo,
Regen
Pr
8.31
= On (1),
Pr
8.32
and Pr
8.33
= OFF (0)
Update rate
Background read
8.39
T28 & T29 digital input auto-selection disable
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
OFF (0)
Update rate
Background read
Reference select Pr 1.14
Pr 8.25 set to:
Pr 8.26 set to:
0, A1.A2 Reference selection by terminal input
Pr
1.41
- Analog ref 2 select
Pr
6.31
- jog
1, A1.Pr
Analog reference 1 or presets selected by terminal input
Pr
1.45
- preset select bit 0
Pr
1.46
- preset select bit 1
2, A2.Pr
Analog reference 2 or presets selected by terminal input
Pr
1.45
- preset select bit 0
Pr
1.46
- preset select bit 1
3, Pr
Preset reference selected by terminal input
Pr
1.45
- preset select bit 0
Pr
1.46
- preset select bit 1
4, Pad
Keypad reference selected
Pr
1.41
- Analog ref 2 select
Pr
6.31
- jog
5, Prc
Precision reference selected
Pr
1.41
- Analog ref 2 select
Pr
6.31
- jog