Unidrive SP has a dedicated hardware enable/secure disable input which always controls Pr
6.29
. If the enable is inactive the IGBT firing signals are
turned off without software intervention. As default (Pr
8.10
= 0) the drive is in the inhibit mode when the enable is inactive. Setting this parameter to
one causes the enable to behave as an Et trip input. When the input becomes inactive an Et trip is initiated. This does not affect Pr
10.32
(Et trip
parameter), therefore an Et trip can be initiated in this mode either by making the enable inactive or setting Pr
10.32
to one.
OFF (0) = Non-inverted
On (1) = Inverted
This word is used to determine the status of the digital I/O by reading one parameter. The bits in this word reflect the state of Pr
8.01
to Pr
8.09
.
8.10
Drive enable mode select
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo,
Regen
OFF (0)
Update rate
Background read
8.11
T24 digital I/O 1 invert
8.12
T25 digital I/O 2 invert
8.13
T26 digital I/O 3 invert
8.14
T27 digital input 4 invert
8.15
T28 digital input 5 invert
8.16
T29 digital input 6 invert
8.17
Relay source invert
8.18
T22 24V output source invert
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
Regen
Pr
8.11
to Pr
8.17
= OFF (0), Pr
8.18
= On (1)
Update rate
4ms read
8.20
Digital I/O read word
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to 511
Update rate
Background write
Bit
Digital I/O
0
T24 input / output 1
1
T25 input / output 2
2
T26 input / output 3
3
T27 input 4
4
T28 input 5
5
T29 input 6
6
Relay
7
T22 24V output
8
Secure disable