Menu 21
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
364
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
21.25
Motor saturation breakpoint 1
Drive modes
Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
Closed-loop vector
0 to 100% of rated flux
Default
Closed-loop vector
50
Normal
parameter
Closed-loop vector
Pr
5.29
Update rate
Background read
21.26
Motor saturation breakpoint 2
Drive modes
Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
Closed-loop vector
0 to 100% of rated flux
Default
Closed-loop vector
75
Normal
parameter
Closed-loop vector
Pr
5.30
Update rate
Background read
21.27
Motoring current limit
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to MOTOR2_CURRENT_LIMIT_MAX %
Default
Open-loop
Closed-loop vector, Servo, Regen
165.0*
175.0*
Normal
parameter
Open-loop, Closed-loop vector, Servo,
Regen
Pr
4.05
Update rate
Background read
21.28
Regen current limit
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
0 to MOTOR2_CURRENT_LIMIT_MAX %
Default
Open-loop
Closed-loop vector, Servo, Regen
165.0*
175.0*
Normal
parameter
Open-loop, Closed-loop vector, Servo,
Regen
Pr
4.06
Update rate
Background read
Содержание unidrive sp