Menus 15 to 17
SM-I/O Plus
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
294
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
This word is used to determine the status of the digital I/O by reading one parameter. The bits in this word reflect the state of Pr
x.03
to Pr
x.10
.
This parameter changes the logic polarity for digital inputs, but not digital outputs or relay outputs.
x.20
Digital I/O read word
RO
Uni
NC
PT
US
Ú
0 to 511
Ö
Update rate: 8ms x number of dumb modules
Bit
Digital I/O
Parameter
0
T2 (I/O 1)
x.09
1
T3 (I/O 2)
x.10
2
T4 (I/O 3)
x.03
3
T6 (DI 4)
x.04
4
T7 (DI 5)
x.05
5
T8 (DI 6)
x.06
6
T21/T22 (Relay 1)
x.07
7
T22/23 (Relay 2)
x.08
x.21
T2 digital I/O 1 source/destination
x.22
T3 digital I/O 2 source/destination
x.23
T4 digital I/O 3 source/destination
x.24
T6 digital input 4 destination
x.25
T7 digital input 5 destination
x.26
T8 digital input 6 destination
x.27
Relay 1 source
x.28
Relay 2 source
RW
Uni
DE
PT
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on drive reset
x.29
Input polarity select
RW
Bit
DE
PT
US
Ú
OFF (0) or On (1)
Ö
On (1)
Update rate: Background read
Pr x.29=0 (negative logic)
Pr x.29=1 (positive logic)
Inputs
<5V = 1, >15V = 0
<5V = 0, >15V = 1
Non-relay outputs 1 = >15V (high side drivers only)
1 = >15V (high side drivers only)
Relay outputs
0 = open, 1 = closed
0 = open, 1 = closed
x.31
T2 digital I/O 1 output select
x.32
T3 digital I/O 2 output select
x.33
T4 digital I/O 3 output select
RW
Bit
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: Background read
Programmable digital inputs and output
Terminal
Input
Destination
/ Source
State
Invert
Output
select
2
I/O 1
Pr
x.21
Pr
x.09
Pr
x.11
Pr
x.31
3
I/O 2
Pr
x.22
Pr
x.10
Pr
x.12
Pr
x.32
4
I/O 3
Pr
x.23
Pr
x.03
Pr
x.13
Pr
x.33