Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance
RFC mode
Unidrive SP Advanced User Guide
403
Issue Number: 10 www.controltechniques.com
7.1.5 Drive address
The drive only acts on messages received that contain a drive address if
the whole drive address or drive group address match the whole
address or the group address in the message, or if the address in the
message is 0 (i.e. a global message). Global or group addressing allows
data to be written to more than one drive with one command. The drive
does not give a response to a global or group write message. Although it
is possible to perform a global or group read, this would result in
messages crashing if more than one drive responds to the command.
7.1.6 Short commands
The following short commands can be used:
This is the same as requesting the value of the last parameter to be read
or written to. The response is the same as for a normal read.
This is the same as requesting the value of the parameter after the last
parameter to be read or written to. The response is the same as for a
normal read.
This is the same as requesting the value of the parameter before the last
parameter to be read or written to. The response is the same as for a
normal read.
Writes to the specified parameter at the same drive address as used by
the last read or write.
All the short commands will only read from the drive or write to the drive
if a valid address has already been sent to the drive in a previous
command. The address is registered as being valid once a read or write
command has been completed provide the address was valid for the
drive even if the parameter does not exist. The valid address is
cancelled if a message is received for a non-valid address or one of the
following occurs:
1. The command is aborted because a non-numerical value is received
in the drive address, menu or parameter numbers.
2. The command is aborted because the two digits for drive address 1
st
digit, drive address 2
nd
digit, menu number or parameter number are
not the same as each other.
3. EOT is received.
4. A character other than NAK, ACK, BS or STX is sent as a short
command.
5. A character other than ENQ is sent at the end of a read command.
7.1.7 Summary of control characters
7.2 CT Modbus RTU specification
This section describes the adaptation of the MODBUS RTU protocol
offered on Control Techniques' products. The portable software class
which implements this protocol is also defined.
MODBUS RTU is a master slave system with half-duplex message
exchange. The Control Techniques (CT) implementation supports the
core function codes to read and write registers. A scheme to map
between MODBUS registers and CT parameters is defined. The CT
implementation also defines a 32bit extension to the standard 16bit
register data format.
Drive address
Message
address
Command
Action
7.8
7.8
Read
Read
7.8
7.8
Write
Write
7.8
7.0
Read
Read
7.8
7.0
Write
Write with no
response
7.8
0.0
Read
Read
7.8
0.0
Write
Write with no
response
NAK
Not acknowledge (Ctl U)
ACK
Acknowledge (Ctl F)
BS
Back space (Ctl H)
STX
Start of text (Ctl B)
M1
Menu number: 1
st
digit
M2
Menu number: 2
nd
digit
P1
Parameter number: 1
st
digit
P2
Parameter number: 2
nd
digit
D1
Data: 1
st
digit
D2
Data: 2
nd
digit
-
-
Dn
Data: n
th
digit
ETX
End of text (Ctl C)
Checksum
ASCII code
Ctl code
STX
Start of text
02
B
ETX
End of text
03
C
EOT
End of transmission
04
D
ENQ
Enquiry
05
E
ACK
Acknowledge
06
F
BS
Back space
08
H
NAK
Not acknowledge
15