Table 4-10. Redundancy configuration
Table 4-11. Configuration
Item
Description
Primary Device ID
Backup Device ID
Each device has a unique identification number.
Redundancy Status
If status is OK, a green check box is displayed. You may expand the Status list to
view further details. In case status is not OK, a list of warnings and errors will be
displayed.
Manual switch over
Active/Passive mode can be changed manually. The Active device
communicates with the host system and responds to requests for
measurement data, status information, and diagnostics. This option can be
useful for testing that both system hubs function properly as Active and
Passive.
Configuration
See
below.
Unpair
It is possible to un-pair the two devices in the redundancy system. When
un-pairing the redundant system hubs, the active device will change mode to
standalone. The passive device will load the default configuration database and
the default Modbus address (245) to make sure it will not disturb
communication on Host and Field ports after unpairing the system hubs.
Item
Description
Common Modbus Address
Common Modbus address is the standard setting. Primary and Backup system
hubs use the same Modbus address.You may use this option in case Primary
and Backup system hubs are connected to different host ports. Then the same
Modbus address can be used instead of individual addresses.
Specific Modbus Address for
Primary Device /
Specific Modbus Address for
Backup Device
The redundant system hubs can be given individual Modbus addresses in case
you need to be able to communicate separately with each system hub.
This is
useful, for example, for verifying the current status of each device.
Passive device responds on
common address
“Passive device communication” on page 79
.
Max Fail-Overs per Hour
Maximum number of fail-overs per hour in order to prevent an oscillating
behavior i.e. switching back and forth between Primary and Backup device. In
case fail-overs tend to occur frequently, the reason behind should be
investigated and fixed.
Fail-over criteria
Take-over criteria
“Take-over criteria” on page 79
.
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......