106
Reference Manual
00809-0100-2460, Rev DE
October 2018
No contact with the
Rosemount 2460 System
Hub
Configuration of
communication protocol
In TankMaster WinSetup/Protocol Channel
Properties:
check that the protocol channel is enabled
check the protocol channel configuration (port,
parameters, modem).
Wrong communication
settings
Use TankMaster to check communication settings.
For TRL2 modems: Baud Rate=4800, Data bits per
character=8, Stop bits=1, no parity.
See
Connected to wrong modem
port
Check which modem is used. Port 7-8 are used for
Host communication. Ports 5-6 can be used for Host
or field device communication depending on
configuration.
Hardware failure
Check the Rosemount 2460 Error LED for
information.
Check the Field Bus Modem.
Check the communication port on the control room
PC.
Contact Emerson Automation
Solutions/Rosemount Tank Gauging service
department.
Impossible to change
configuration (write to
Holding Registers) of the
Rosemount 2460 database
The Rosemount 2460 is write
protected
Check hardware write protection switch (see
)
Check software write protection in TankMaster
WinSetup
Configuration locked by other
host system
Retry after a couple of minutes
Process value is invalid
Process value is not valid
Check status in Input Registers for the failing field
device
All process values are invalid
Check device status/error Input Registers for the
failing field device
Connected devices don’t
respond to request
The Rosemount 2460 tank
database is not configured
Configure Tank Database with TankMaster
WinSetup
Bad cabling or wrong polarity
Check or change cables
Wrong communication
settings
Use TankMaster to check communication settings.
For TRL2 modems: Baud Rate=4800, Data bits per
character=8, Stop bits=1, no parity
See
The Rosemount 2460 is
connected to wrong modem
port
Check which modem is used. Ports 1-4 are used for
field devices. Port 7-8 are used for host
communication. Ports 5-6 can be used for host or
field device communication depending on
configuration.
Mismatch between Modbus
address in field device and
Rosemount 2460 tank
database
Make sure that the Modbus address of the field
device is configured for the right tank in the Tank
Database of the Rosemount 2460.
See
“Tank Database configuration” on page 62
Symptom
Possible cause
Action (continued)
Содержание Rosemount 2460
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2460 Rev DE Title Page October 2018 Title Page ...
Страница 12: ...x Reference Manual 00809 0100 2460 Rev DE Contents October 2018 Contents ...
Страница 18: ...6 Reference Manual 00809 0100 2460 Rev DE Introduction October 2018 Introduction ...
Страница 60: ...48 Reference Manual 00809 0100 2460 Rev DE Installation October 2018 Installation ...
Страница 100: ...88 Reference Manual 00809 0100 2460 Rev DE Configuration October 2018 Configuration ...
Страница 182: ...170 Product Certifications Product Certifications October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 214: ...202 Modbus Standard Question Modbus Standard Question October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 230: ...218 Varec Device Configuration Varec Device Configuration October 2018 Reference Manual 00809 0100 2460 Rev DE ...
Страница 238: ...226 Reference Manual 00809 0100 2460 Rev DE Index October 2018 Index ...
Страница 239: ......