141
Reference Manual
00809-0100-2460, Rev DE
October 2018
6.21.2
To unpair redundant system hubs
1. Open the Web Graphical User Interface (GUI). See section
“Using the web interface” on page 114
) for
more information on how to use the Web GUI.
2. Select the Redundancy menu option.
3. Expand the Unpair option and verify that a green symbol indicates that the Primary and Backup
devices can be unpaired.
4. Click the
Unpair
button.
5. Verify that the redundant system hubs are successfully unpaired and changed to standalone mode.